And p, May be greater than p, Corresponds to the range for the 20-4 ma current – Burkert Type 8076 User Manual

Page 54

Advertising
background image

52

Adjustmentandcommissioning

Param

Outputs

AC1 / AC2

This is
when the
device is be-
ing parame-
tered............
....................

This is
when the
device is be-
ing parame-
tered............
....................

PVar:

4mA:

INPUT

20mA:

INPUT

Filter:

Slow

Fast

None

Diag. mode:

None

22mA

Flow_L

Flow_m3

Flow_gal

Flow_Igal

Freq.

Tot1_L

Tot1_m3

Tot1_gal

Tot1_Igal

Tot2_L

Tot2_m3

Tot2_gal

Tot2_Igal

Functions "4mA" and "20mA" are used to define the measurement range for the flow rate, the input frequency or
the totalizer associated with the current on the 4-20 mA output.

P

1

and P

2

are the values associated with a current of 4 mA or 20 mA respectively: P

1

may be greater than P

2

: if

this is the case, the signal is inverted and range P

1

-P

2

corresponds to the range for the 20-4 mA current.

mA

0

20

4

P

2

P

1

Flow rate, input frequency or totalizer chosen

Figure 40 :

4-20 mA current according to the chosen physical parameter or totalizer

PVAR: Choose a physical parameter (flow rate volume unit or input frequency) or a totalizer combined with
current output 1 or current output 2 respectively.
4mA: Choose the value of the physical parameter or the totalizer (previously selected) and the flow time unit,
combined with a current of 4 mA for each current output. See “Current output parameters”, next page.
20mA: Choose the value of the physical parameter or the totalizer (previously selected) and the flow time unit,
combined with a current of 20 mA for each current output. See “Current output parameters”, next page.
FILTER: choose the level of damping for the fluctuations of the current value for each current output. Three
damping levels are proposed: "slow", "fast" or "none".

The damping for the current outputs is similar to the damping of the display. See Figure 39.
DIAG MODE: choose to emit a current of 22 mA on the current output selected when an "error" event related
to diagnostics (see chap. 9.14.2 and ) is generated by the device or allow the current output to operate normally
(choose "none").