Burkert Type 8076 User Manual

Page 61

Advertising
background image

59

Adjustmentandcommissioning

Detailed procedure of a teach-in by flow rate (“flow.teach” function in the “sensor” menu)

Choose the volume unit in which the teach-in is run:

Calib

Sensor

Flow_L

Flow_m3

Flow_gal

Flow_Igal

PVar:

Flow Teach

Freq.

Run the teach-in:

Establish the flow in the pipe and wait until it is
stabilised.

Save the new K
factor calculated or
not.

Flow Teach

Sensor

Start Teach

Calib

0005 L/min

Measure

K teached:

K=3,810

Cal. Result

BACK

Save: Yes/No

Cal. Result

The device displays the K factor

calculated by teach-in.

OK

The device calculates the flow measured
in the pipe, with the current K factor, for
100 seconds

1)

.

The bargraph shows the time passed.

FlowTeach

0049 L/min
0001 L/s

The device displays the average flow rate

calculated with the current K factor.

Enter the value of the flow in
the pipe.

Modify the time unit if
necessary.

OK

K teached set to

max K=9999

BACK

Confirm the K factor =9999 with “YES”
or keep the current K factor with “NO”.

Save modified

data? Yes/No

If the calculated K factor
is ≥ 9999, it is forced to
9999.

1)

Measurement can be suspended at any time by selecting “OK”.