Calibration menu, Activating/deactivating the hold function, Modifying the calibration menu access code – Burkert Type 8076 User Manual

Page 57

Advertising
background image

55

Adjustmentandcommissioning

9.13. calibration menu

9.13.1. Activating/deactivating the hold function

See chap. 9.10 to access the Calib menu.

System

Calib

Hold

Hold: Disable

Hold: Enable

The Hold mode is automatically deactivated when the device restarts after a power interruption, if the
Hold mode was activated at the moment of the power cut-off.

The Hold mode is used to carry out maintenance work without interrupting the process.

To activate the HOLD mode:

access the "HOLD" function;

choose "enabled";

confirm by "OK".

In practice, when the device is in Hold mode:

• the

HOLD

!

icon is displayed in place of the

icon;

• the current emitted on each 4-20 mA output is fixed at the value of the last measurement of the physical para-

meter associated with each output;

• each transistor output is fixed at the status acquired at the moment the Hold function is activated;

The Hold mode has no effect on the transistor outputs when they are operating in “Pulse” mode. See
chap. 9.12.10.

• the device is in Hold mode until the HOLD function is deactivated.

To deactivate the HOLD mode:

access the "HOLD" function;

choose "disabled";

confirm by "OK".

9.13.2. modifying the calibration menu access code

See chap. 9.10 to access the Calib menu. The default access code is "0000".

Enter the new
access code to
the CALIB menu

Confirm the new
code

System

Calib

Code

0***

Confirm

0***

English

Type 8026- 8036- 8076

Advertising
This manual is related to the following products: