Adjustmentandcommissioning

Switching only occurs if one of the thresholds, high or low (functions "High" or "Low"), is exceeded for a duration
longer than this time delay.
PULSE: When the choice “Pulse” is selected in MODE function above, enter here the volume of fluid for which a
pulse must be transmitted on transistor output 1 or transistor output 2 respectively.

hysteresis operating

The output status changes when a threshold is reached:

• by increasing flow rate, the output status changes when the high threshold ("high") is reached.

• by decreasing flow rate, the output status changes when the low threshold ("low") is reached.

ON

OFF

contact

Low High

physical parameter or
totalizer

NO

1)

ON

OFF

contact

Low High

physical parameter or
totalizer

NC

1)

Figure 41 :

Hysteresis operating

NO = Normally open ; NC = Normally closed
Window operating (choice "Window"):

The change of status occurs whenever one of the thresholds is detected.

ON

OFF

contact

Low High

physical parameter or
totalizer

NO

1)

ON

OFF

contact

Low High

physical parameter or totalizer

NC

1)

Figure 42 :

Window operating

1)

NO = Normally open ; NC = Normally closed

pulse operating (choice "pulse")

This function is used to generate a pulse on the transistor output each time a predetermined volume of fluid passes.

Enter the desired fluid volume and, if necessary, modify the volume units/pulse in the “PULSE” function in the “Output.
TR1” or “Output.TR2” menu

• A “Warning” event is emitted and the message “W:TRnPu too big” is displayed when the volume

entered multiplied by the K factor of the device > 1000000.

• A “Warning” event is emitted and the message “W:TRnPu 1:1:set” is displayed when the volume

entered multiplied by the K factor of the device < 1. In this case, the pulse frequency is forced to the
value of the input frequency.