9.12.10. setting the parameters of the transistor outputs

See chap. 9.10 to access the Param menu. The 2nd transistor output "TR2" is only available on a version with 2
transistor outputs.

Param

TR1 / TR2

PVar:

Mode:

Hysteresis

Low:

INPUT

Contact:

Normally open

Normally closed

Window

High:

INPUT

Delay:

INPUT

Outputs

Pulse

Flow_L

Flow_m3

Flow_gal

Flow_Igal

Freq.

Tot1_L

Tot1_m3

Tot1_gal

Tot1_Igal

Tot2_L

Tot2_m3

Tot2_gal

Tot2_Igal

Warning

If "Mode" ≠ "Pulse"

Pulse:

INPUT

If "PVar" ≠ "Warning"

If "Mode" ≠ "Pulse"

If "Mode" = "Pulse"

This is
when the
device is be-
ing parame-
tered............
....................

This is
when the
device is be-
ing parame-
tered............
....................


PVAR: Choose a physical parameter (flow rate volume unit or input frequency) or a totalizer associated with tran-
sistor output 1 or transistor output 2 respectively or associate the “warning” event (see chap. 9.14.2) with tran-
sistor output 1 or transistor output 2 respectively. If the selected transistor output is linked to the "warning" event,
the transistor switches as soon as such an event is generated by the device.
MODE: Choose either the hysteresis or window operating mode, for transistor output 1 or transistor output 2, or
operating on pulse mode (choice “Pulse”) for transistor output 1 or transistor output 2.
LOW: enter the low switching threshold value for transistor output 1 or transistor output 2, as well as the flow rate
time unit. See details on next page.
HIGH: enter the high switching threshold value for transistor output 1 or transistor output 2, as well as the flow
rate time unit. See details on next page.
CONTACT: choose the type of off-position (normally open, NO, or normally closed, NC) for transistor output 1 or
transistor output 2. See details on next page.
DELAY: choose the value of the time delay prior to switching (from 0 to 60 s) for each transistor output.The time
delay before switching is applicable to both switching thresholds.