Is generated by the device – Burkert Type 8035 User Manual

Page 101

Advertising
background image

99

Operatingandfunctions

9.7.25 Configuring the relay output Do3 to control an auxiliary

valve

• Connect the auxiliary valve (installed into the pipe with low flow rate) to the relay output DO3. See chap.

“7.6.12”.

• The time delay before opening the auxiliary valve is the same as the time delay before opening the main

valve.

• If no auxiliary valve is necessary, enter a filling rate of 100 in the settings of the relay output DO2.

If the filling rate associated to the relay output DO2 is < 100, the relay output DO3 is automatically configured to
control the auxiliary valve that completes the filling up to 100.

OUtPUt

VALVE

DO3

DO4

Confirm.

iNV YES

iNV NO

0......9

Choose the operating, inverted or not inverted, of the relay output.

Figure 83:

Configuring the relay output DO3 to control an auxiliary valve

If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press

ENTER

to save the settings or not and go back to the Process level.

9.7.26 Configuring the transistor output Do4 to transmit the

device state and activating / deactivating the generation of
a 10 Hz frequency when an error message is generated by
the device

The transistor output DO4 can be configured to transmit the device state to a LED or a remote instrument (PLC
for example).

If, furthermore, the device signals an operating error (see chap. “10.3.2”), the transistor output DO4 can be con-
figured to generate a 10 Hz-frequency.

The following states are transmitted:

State of the device

State of the the transistor output DO4

No dosing being done

OFF

Dosing being done

ON

Dosing interrupted

1 Hz-frequency

English

Type 8025 - 8035 BATCH

Advertising
This manual is related to the following products: