9 configuring the dosing mode "ext. mem, 10 configuring the dosing mode "ext. +loc, 11 configuring the dosing mode "ext. [t – Burkert Type 8035 User Manual

Page 85: Configuring the dosing mode "ext. mem, Configuring the dosing mode "ext. +loc, Configuring the dosing mode "ext. [t

Advertising
background image

83

Operatingandfunctions

9.7.9

Configuring the dosing mode "exT. mem."

This dosing mode allows for starting the dosing, via the digital inputs, of a quantity saved in the memory.

OPtiONAL

MODE

EXt. MEM.

Confirm.

VOLUMES

Confirm.

Enter up to 7 dosing quantities into the memory. See chap. “9.7.14”.

Figure 64:

Configuring the dosing mode "EXT. MEM."

If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press

ENTER

to save the settings or not and go back to the Process level.

9.7.10 Configuring the dosing mode "exT. +loC"

This dosing mode allows for selecting a quantity saved in the memory, via the navigation keys (or via the digital
inputs), then starting the dosing via the digital input DI4.

OPtiONAL

MODE

EXt. +LOC.

Confirm.

VOLUMES

Confirm.

Enter up to 7 dosing quantities into the memory. See chap. “9.7.14”.

Figure 65:

Configuring the dosing mode "EXT. +LOC."

If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press

ENTER

to save the settings or not and go back to the Process level.

9.7.11 Configuring the dosing mode "exT. [T]"

• In this mode, the dosing starts as soon as the digital input DI1 is switched.

• If the conditions for calculating A and B are not respected, an alarm ERROR [T] will be generated

and the device will abort the current dosing.

English

Type 8025 - 8035 BATCH

Advertising
This manual is related to the following products: