If a warning message is generated by the device and no dosing is being done, a long pulse (> 2
seconds) on DI4 allows for remotely accessing to the Information menu, whatever the state of the inputs
DI1 to DI3. See chap. “9.11”.

Process level (the digital inputs DI1, DI2 and DI3 are deactived).

To choose the dosing quantity from the memory, activate the digital inputs DI1,
DI2, DI3:

State of input DI3

0

0

0

1

1

1

1

State of input DI2

0

1

1

0

0

1

1

State of input DI1

1

0

1

0

1

0

1

Associated quantity

V1

V2

V3

V4

V5

V6

V7

To go back to the Process level, deactivate the 3 digital inputs DI1 to DI3.

The display alternately shows the called memory and the dosing quantity.

To start the dosing, send a short pulse (< 2 s) on the digital input DI4.

V1

0120.0 L

The dosing quantity is counted down (the dosing units blink).

To read the flow rate measured in the pipe, press

or

0......9

.

To read the total dosing quantity, press

or

0......9

once.

To interrupt the dosing, see “Figure 43”.

37.8L

1156 L

V1

When the dosing is finished, the device is ready for a new dosing.

To go back to the Process level, deactivate the 3 digital inputs DI1 to DI3.

Figure 45:

Doing a dosing of a quantity from the memory via the digital inputs, in dosing mode "EXT.+LOC."