5 wiring a panel version, 6 wiring a wall-mounted version, Wiring a panel version – Burkert Type 8035 User Manual

Page 39: Wiring a wall-mounted version

Advertising
background image

37

Installationandwiring

7.6.5

Wiring a panel version

Only move the selectors when the power supply is off.

Install the device as described in chap. “7.3”.

Set the selectors "SENSOR TYPE", "SENSOR SUPPLY" and "LOAD": see chap. “7.6.7”.

Before wiring the device insert the supplied cable clips into the slots of
the electronic board.

Figure 25:

Inserting the cable clips

Wire acc. to chap. “7.6.7”, “7.6.9”, “7.6.12” and “9.6”.

Secure the power supply cable, the flow sensor connection cable and the relay connection cables, with the
cable clips.

7.6.6

Wiring a wall-mounted version

Only move the selectors when the power supply is off.

Insert the supplied stopper gaskets into the unused cable glands to ensure the tightness of the device.

• Unscrew the unused cable gland.

• Remove the transparent disk.

• Insert the supplied stopper gasket.

• Screw the nut of the cable gland.

Install the device as described in chap. “7.4”.

Set the selectors "SENSOR TYPE", "SENSOR SUPPLY" and "LOAD": see chap. “7.6.7”.

If the wall-mounted version is energized with a 115/230 V AC power supply, set selector D

as shown in

“Figure 26”

.

Selector D makes it possible to configure the supply voltage of the device in a 115/230 V AC version.

Energize the device with a
230 V AC voltage.

Energize the device with a
115 V AC voltage.

D

230V

115V

Figure 26:

Selector of the supply voltage on a 115/230 V AC version

Loosen the nuts of the cable glands.