English, 33 installationandwiring – Burkert Type 8035 User Manual

Page 35

Advertising
background image

33

Installationandwiring

LNLN

230V230V230V

1

A

2

3

B

C

CURRENT

SOURCE

SINK

BINARY

PE

PE

PE

PE

DI1

DI2

DI3

DI4

DO4

ISOG

FLOW

SENSOR

L+

L-

PE P- P+

NC

Iout

PULSE

DO1

Supply

12..36Vdc

Univ

Batch

(AO1)

SUPPLY

NC

COIL

PULSE INPUT

NPN/PN

P

2

1

3

PE

+

-

SENSOR

SUPPL

Y

LOAD

+5V

L+

(L+)-12V

COIL/PNP

39K

470

2.2K

SENSOR TYPE

COIL

NPN/PNP

DO2

DO3

OFF

ON

5

6

D

7

8

4

T 125 mA

terminal block 1

PE: shieldings of the power supply cable and the input /
output cables
terminal block 2

• NC: not connected

• L+: V+ (red wire, factory wired)

• L-: 0V (black wire, factory wired)

• PE: protective earth (green/yellow wire, factory wired)

• P-: negative transistor output (DO1)

• P+: positive transistor output (DO1)

connector 3: connection of the flow sensor
terminal block 4 "binAry"

• DI1 to DI4: 4 digital inputs

• DO4: transistor output

• ISOG: ISOGND, ground common to the 4 digital inputs

and the transistor output DO4.

• PE: cable shielding

terminal block 5: wiring the DO2 relay output.
terminal block 6: wiring the DO3 relay output.
terminal block 7: wiring of the 115/230 V AC
power supply

mark 8 : time-delay fuse to protect the
115/230 V AC power supply

selector A : see chap. “7.6.4”;

selector B : see chap. “7.6.4”;

selector C : see chap. “7.6.4”.

selector D : see chap. “7.6.4”.

Figure 20:

Terminal assignment of a 115/230 V AC fed compact version

English

Type 8025 - 8035 BATCH

Advertising
This manual is related to the following products: