T250 ma, English, 34 installationandwiring – Burkert Type 8035 User Manual

Page 36

Advertising
background image

34

Installationandwiring

230V

L N

230V

T

250 mA

5 6 7 8 9 10

L N

230V

1

A

2

4

B

C

CURRENT

SOURCE

SINK

BINARY

PE

PE

PE

PE

DI1

DI2

DI3

DI4

DO4

ISOG

FLOW

SENSOR

L+

L-

PE P- P+

NC

Iout

PULSE

DO1

Supply

12..36Vdc

Univ

Batch

(AO1)

SUPPLY

NC

COIL

PULSE INPUT

NPN/PN

P

2

1

3

PE

+

-

SENSOR

SUPPL

Y

LOAD

+5V

L+

(L+)-12V

COIL/PNP

39K

470

2.2K

SENSOR TYPE

COIL

NPN/PNP

DO2

DO3

OFF

ON

5

6

D

7

8

9

3

terminal block 1

PE: factory wired shield.
terminal block 2

• NC: not connected

• L+: V+ (red wire, factory wired)

• L-: 0V (black wire, factory wired)

• PE: protective earth, factory wired

• P-: negative transistor output (DO1) (brown wire, factory

wired)

• P+: positive transistor output (DO1) (white wire, factory

wired)

terminal block 3 "binAry"

• DI1 to DI4: 4 digital inputs

• DO4: transistor output

• ISOG: ISOGND, ground common to the 4 digital inputs

and the transistor output DO4.

• PE: cable shielding

terminal block 4 "floW sensor": Wiring the remote
flow sensor. The wiring depends on the type of output
signal originating from the flow sensor: see chap. “7.6.7”.

terminal block 5: wiring the DO2 relay output.
terminal block 6: wiring the DO3 relay output.
terminal block 7

• terminal 5 not connected

• terminal 6: positive 27 V DC power supply,

available to energize an external instrument

• terminal 7: 0V (earth of the power supply

available to energize an external instrument)

• terminal 8: protective earth for the cable

shieldings

• terminal 9: negative transistor output (DO1)

• terminal 10: positive transistor output (DO1)

terminal block 8: wiring of the 115/230 V AC
power supply

mark 9 : time-delay fuse to protect the
115/230 V AC power supply

selector A : see chap. “7.6.7”.

selector B : see “Table 5”, page 40.

selector C : see chap. “7.6.7”.

selector D : see chap. “7.6.7”.

Figure 21:

Terminal assignment of a wall-mounted version, 115/230 V AC

English

Type 8025 - 8035 BATCH

Advertising
This manual is related to the following products: