Operatingandfunctions

9.7.17 Activating / deactivating the generation of alarms for

problems occuring at the end of a dosing

When the following 3 criteria are fulfilled the dosing is finished:

• no flow rate measured in the pipe,

• the valves are closed,

• and the quantity has entirely been dosed.

If a flow rate is measured in the pipe whereas the valves should be closed (once the dosing is finished or when a
dosing has been interrupted), an alarm can be generated.

When an alarm is generated, the device stops the process:

• the valves connected to the relay outputs DO2 and DO3 are closed,

• the device state LED becomes orange and flashes fast,

• a 3,5 Hz-frequency is generated on the transistor output DO4 if it is configured to transmit the state of the

device (see chap. “9.7.26”),

• the outputs configured with the function "ALARM" are switched (see chap. 9.7.19),

• the message "ALARM" is displayed.

Activate or deactivate the generation of an alarm when a flow rate is
measured in the pipe whereas the valves are closed.

Confirm.

ALARM

AFtER

REtURN

DEL. = 001

If the generation of alarms has been activated, enter the duration the
problem must be present (value between 1 and 200 s) before gener-
ating the alarm.

Confirm.

DiSABLE

ENABLE

0......9

Figure 74:

Activating / deactivating the generation of alarms for problems occuring at the end of a dosing

If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press

ENTER

to save the settings or not and go back to the Process level.

English

Type 8025 - 8035 BATCH