Burkert Type 8035 User Manual

Page 122

Advertising
background image

120

Maintenanceandtroubleshooting

Device state
leD

output Do4 in
"stAte" mode

message
displayed

possible cause

recommended action

any colour

-

"PU H LIM"

The message is displayed after
the pulse value has been entered
(parameter "PU" of the transistor
output DO1) or upon validation
of the settings of the Parameters
menu.

The pulse value times the K factor
of the device is < 1.

The quantity entered for a pulse is
too low.

Enter a higher quantity
per pulse. See chap.
“9.7.22”.

any colour

flashes at a 10 Hz-
frequency for 2
seconds after
the device has
been energized,
then flashes at a
1 Hz-frequency

"CONTINUE" The power supply has been cut

during a dosing

the dosing has been interrupted.

Check the electrical
installation.

Abort the current
dosing or continue the
dosing: in that case
check that the current
dosing is correct.

any colour

flashes at a 10 Hz-
frequency for 2 s
then flashes at a
1 Hz-frequency

Process
level

The power supply has been cut
during the consultation of the
messages of the Information menu
via the digital inputs.

Check that the PLC
knows that the device
has returned to the
Process level.

English

Type 8025 - 8035 BATCH

Advertising
This manual is related to the following products: