A dosing – Burkert Type 8035 User Manual

Page 93

Advertising
background image

91

Operatingandfunctions

9.7.16 Activating / deactivating the generation of alarms for

problems occuring during a dosing

The following problems can occur during a dosing:

• no flow in the pipe whereas the valves are open.

• a flow is measured in the pipe whereas the valves are closed.

These problems can be signalled by the generation of an alarm.

When an alarm is generated, the device stops the process:

• the valves connected to the relay outputs DO2 and DO3 are closed,

• the device state LED becomes orange and flashes fast,

• a 3,5 Hz-frequency is generated on the transistor output DO4 if it is configured to transmit the state of the

device (see chap. “9.7.26”),

• the outputs configured with the function "ALARM" are switched (see chap. 9.7.19),

• the message "ALARM" is displayed.

Activate or deactivate the generation of an alarm when no flow rate is
measured in the pipe whereas the valves are open.

Confirm.

ALARM

DURiNG

AFtER

DEL. = 001

If the generation of alarms has been activated, enter the duration the
problem must be present (value between 1 and 200 s) before gener-
ating the alarm.

Confirm.

DiSABLE

ENABLE

0......9

Figure 73:

Activating / deactivating the generation of alarms for problems occuring during a dosing

If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press

ENTER

to save the settings or not and go back to the Process level.

English

Type 8025 - 8035 BATCH