95

Operatingandfunctions

9.7.20 Configuring the transistor output Do1 or Do4 or the relay

output Do3 to switch when a warning message is emitted
by the device

When the device generates a warning message, the device state LED is orange.

The generation of a warning message can be indicated by the switching of the output DO1 and/or DO3 and/or
DO4.

The relay output DO3 can be configured to switch when a warning message is generated by the device, if
the output is not configured to control an auxiliary valve. See chap. “9.7.25”.

REtURN

OUtPUt

DO1

WARNiNG

DO2

iNV YES

iNV NO

0......9

Choose the operating, inverted or not inverted, of the
output.

Confirm.

DO3

DO4

DO4

Figure 78:

Configuring the output DO1 or DO3 or DO4 to indicate the generation of a warning message

If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press

ENTER

to save the settings or not and go back to the Process level.

9.7.21 Configuring the transistor output Do1 or Do4 or the relay

output Do3 to signal the end of the dosing

When the 3 following criteria are fulfilled the dosing is finished:

• the valves are closed (with the exception of a dosing being interrupted),

• no flow rate measured in the pipe,

• and the quantity has entirely been dosed.

The end of a dosing can be signalled by the generation of a 200 ms pulse on the output DO1 and/or DO3 and/or
DO4, if the dosing has not been aborted on purpose or interrupted by the generation of an "ERROR [T]" alarm.

The relay output DO3 can be configured to signal the end of the dosing, if the output is not configured to
control an auxiliary valve. See chap. “9.7.25”.

English

Type 8025 - 8035 BATCH