4 installation of a wall-mounted version, 5 installation of a 8035 batch, Installation of a wall-mounted version – Burkert Type 8035 User Manual

Page 28: Installation of a 8035 batch, Remove the blanking strips covering the screws, Wire acc. to instructions in chap. “7.6, 26 installationandwiring, Figure 13: installation of a wall-mounted version

Advertising
background image

26

Installationandwiring

7.4

installation of a wall-mounted version

note

risk of material damage if the cable glands are not tightly screwed on the housing

▶ Before installing the wall-mounted housing on its support, tighten the nuts of the entry item of the cables

glands at a torque of 1.5 Nm.

The device in a wall-mounted version has 4 holes in the bottom of the housing.

Remove the blanking strips covering the screws.

Blanking strips

ENTER

0....9

FLOW

Nut of the entry item

Loosen the 4 screws and open the cover to get access to the holes [1].

1

1

1

1

106 mm

230V

L N

230V

T 250 mA

5 6 7 8 9 10

L N

230V

CURRENT

SOURCE

SINK

BINARY

PE

PE

PE

PE

DI1

DI2

DI3

DI4

DO4

ISOG

FLOW

SENSOR

L+

L-

PE P- P+

NC

Iout

PULSE

DO1

Supply

12..36Vdc

Univ
Batch

(AO1)

SUPPLY

NC

COIL

PULSE INPUT

NPN/PNP

2

1

3

PE

+

-

SENSOR

SUPP

LY

LOAD

+5V

L+

(L+)-12V

COIL/PNP

39K

470

2.2K

SENSOR TYPE

COIL

NPN/PNP

DO2

DO3

OF

FO

N

106 mm

Figure 13:

Installation of a wall-mounted version

Secure the housing to the support respecting the dimensions indicated in “Figure 13”.

Wire acc. to instructions in chap. “7.6”.

Close the housing and tighten the 4 screws of the cover.

7.5

installation of a 8035 Batch

The electronic module SE35 Batch can be installed on a pipe by using a sensor-fitting S030.

Observe the fluid temperature/pressure dependency depending on the material of the sensor-fitting S030 used:

English

Type 8025 - 8035 BATCH

Advertising