Load – Burkert Type 8035 User Manual

Page 38

Advertising
background image

36

Installationandwiring

Table 4:

Position of selectors "SENSOR TYPE", "SENSOR SUPPLY" and "LOAD" on a compact version

Selector

"SENSOR TYPE"

( C )

Selector "SENSOR SUPPLY"

SENSOR

SUPP

LY

+5V

L+

(L+)-12V

A

Selector "LOAD"

B

LOAD

COIL/PNP

39K

470

2.2K

Set the
selector on
"NPN/PNP"
(“Figure 22”)

The flow sensor of the compact version needs a minimum
voltage supply of 5 V DC :

If the device is fed with a voltage ≥ 12 V DC and
< 17 V DC, set the voltage selector "SENSOR
SUPPLY" on "5V" or "L+".

If the device is fed with a voltage ≥ 17 V DC, the
voltage selector "SENSOR SUPPLY" can be set to any
position.

If the device is fed with a 115/230V AC voltage, set
the voltage selector "SENSOR SUPPLY" on "L+".

Set selector "LOAD":

• either on "2.2k": the load

resistance R is then 2,2 kW

• either on "470": the load

resistance R is then 470 W

If the compact version of the 8025 Batch is energized with a 115/230 V AC power supply, set selector D as
shown in “Figure 23”.

Selector D makes it possible to configure the supply voltage of the device in a 115/230 V AC version.

Energize the device with a
230 V AC voltage.

Energize the device with a
115 V AC voltage.

D

230V

115V

Figure 23:

Selector of the supply voltage on a 115/230 V AC version

Before wiring the device insert the supplied cable clips into the slots of
the electronic board.

Figure 24:

Inserting the cable clips

Install the device as described in chap. “7.2” or “7.5”.

Wire acc. to chap. “7.6.9”, “7.6.12” and “9.6”.

Secure the power supply cable and the relay connection cables, with the cable clips.

Close the housing and tighten the 4 screws of the cover.