13.5.1 Mass flow QM unit


Using this function, the operator can define the physical unit for all display functions, limit values and the
upper-range value of mass flow. After choosing the Mass flow QM unit function and pressing

↵, the fol-

lowing selection field will be displayed:

Mass flow QM unit

[kg/h]


According to the description in Section 12.4.3.1 Selection window/make a selection, one of the following
units can be selected:

¾

kg/s, kg/min, kg/h

¾

t/h

¾

g/min

¾

lbs/s, lbs/min, lbs/h

¾

shton/h

¾

lton/h

Press

↵ to confirm and save the selection.


13.5.2 Mass flow QM range


This function allows the operator to set the upper-range value for mass flow. The upper-range value
takes on the unit defined using the Mass flow unit function. The upper-range value will scale the current
and frequency outputs assigned to mass flow. After choosing the Mass flow QM range function and
pressing

↵, the following selection field will be displayed:

QM range=100%

XXXXX.XX kg/h


The current upper-range value for mass flow will be displayed. According to the description in Section
12.4.3.2 Input window/modify a value, the current value can be changed.

CMB & CT OPERATING MANUAL
Part No 06EN003384 rev. 1.6

Page 63 of 106