Speed comp mode, Timed outputs, 45 pls functions – Electro Cam PL-1746 Series User Manual

Page 90

Advertising
background image

4-45 PLS Functions

Timed Outputs

Backplane

PL-1746 Function Name

SLC 500

Mapping Read/

Valid Range for Data

File

Index

Write

Address

Number

Capability

Time (ms)

M0:S.320-

768-

R/W

0-9999

Channels 0-31,

M0:S.351

830

1word/channel

Screen

MAIN SCREEN

to FUNCTION MENU

to TIMED OUTPUTS

Use numeric entry or INC/DEC to change CHANNEL. Use numeric entry to set TIME in
milliseconds.

Description

Any four outputs can be programmed to time out rather than remain on until an OFF
setpoint is reached. This makes the output duration constant regardless of machine
speed. If the OFF setpoint is reached before the specified time has elapsed, the timing
will be aborted and the output will turn off immediately.
Once an output times out, it will not turn on until the next ON setpoint is reached. Each
timed output can have a unique time delay length.

A timed output must be programmed with ON and OFF position setpoints in order for
output timing to take effect.

If the machine is rotating in the reverse direction, timed outputs will energize when the
OFF edge of the pulse occurs.

Speed Comp Mode

Backplane

PL-1746 Function Name

SLC 500

Mapping Read/

Valid Range for Data

File

Index

Write

Address

Number

Capability

Speed Comp Mode

M0:S.35

198

R/W

0=ONE
1=L/T

Screen

MAIN SCREEN

to CONFIG MENU

to INITIAL SETUP

to SPEED

COMP MODE

Press SEL key to toggle between ONE and L/T. Press ENT to confirm your selection.

Description

Speed Comp Mode determines whether standard or leading/trailing edge speed com-
pensation is in effect. When the Speed Comp Mode is ONE, the same value of speed
comp is used for both leading and trailing edges. When the Speed Comp Mode is “L/T”,
the leading and trailing edges of a pulse may have different values of speed comp.

Also see SPEED COMPENSATION.