Warning:

Use National Electric (NEC)

or other country-specific

standard wiring and safety

practices when wiring and

connecting this controller to

a power source and to elec-

trical sensors or peripheral

devices . Failure to do so may

result in damage to equip-

ment and property, and/or

injury or loss of life .

NOTE: To prevent ground

loops, isolation needs to be

maintained from input to out-

put when using switched DC

or analog process outputs .

CAUTION: Always mount the

controller with the heat-sink

fins aligned vertically .

NOTE: Terminals L4 and

A1 on the limit connector

are jumpered at the factory

to complete the contactor

circuit . Additional switches

may be wired in series to the

terminals .

Ó

WARNING: If high voltage is

applied to a low-voltage con-

troller, irreversible damage

will occur .

Watlow EZ-ZONE

®

ST

18

Chapter 2 Install and Wire

Power

Power

power

power

98
99

CF

CD
CE

B5
D6
D5

Slot C

fuse

• Minimum/Maximum Ratings
• 85 to 264VÅ (ac)
• 20.4 to 26.4 VÅ (ac) / VÎ (dc)
• 47 to 63 Hz
• 12VA maximum power consumption without mechanical contactor in

system

• 50VA maximum power consumption with mechanical contactor in

system, 140VA if using external contactor

Input 1 Thermocouple

-

+

S1
R1

Slot B

• 20 kΩ maximum source resistance
• >20 MΩ input impedance
• 3 microampere open-sensor detection
• Thermocouples are polarity sensitive. The negative lead (usually

red) must be connected to S1.

• To reduce errors, the extension wire for thermocouples must be

of the same alloy as the thermocouple.

ST _ _ - _ _ _ _ - _ _ _ _ (all)

Input 1 RTD

2-wire

S1
R1

S1

S3

Slot B

3-wire

T1
S1
R1

S1

S2

S3

Slot B

• platinum, 100 and 1,000 Ω @ 0°C
• calibration to DIN curve (0.00385 Ω/Ω/°C)
• 20 Ω maximum lead resistance
• RTD excitation current of 0.09 mA typical. Each

ohm of lead resistance may affect the reading by

0.03°C.

• For 3-wire RTDs, the S1 lead (usually white) must

be connected to R1.

• For best accuracy use a 3-wire RTD to compensate

for lead-length resistance. All three lead wires must

have the same resistance.

ST _ _ - _ _ _ _ - _ _ _ _ (all)

Input 1 Process

-

+

S1
R1

volts

Slot B

-

+

T1
S1

amperes

Slot B

• 0 to 20 mA @ 100 Ω input impedance
• 0 to 10VÎ (dc) @ 20 kΩ input impedance
• 0 to 50 mVÎ (dc) @ 20 kΩ input impedance
• scalable
ST _ _ - _ _ _ _ - _ _ _ _ (all)