Wiring a serial eia-485 network – Watlow EZ-ZONE ST User Manual

Page 27

Advertising
background image

Ó

Warning:

Use National Electric (NEC)

or other country-specific

standard wiring and safety

practices when wiring and

connecting this controller to

a power source and to elec-

trical sensors or peripheral

devices . Failure to do so may

result in damage to equip-

ment and property, and/or

injury or loss of life .

NOTE: To prevent ground

loops, isolation needs to be

maintained from input to out-

put when using switched DC

or analog process outputs .

CAUTION: Always mount the

controller with the heat-sink

fins aligned vertically .

NOTE: Terminals L4 and

A1 on the limit connector

are jumpered at the factory

to complete the contactor

circuit . Additional switches

may be wired in series to the

terminals .

Ó

WARNING: If high voltage is

applied to a low-voltage con-

troller, irreversible damage

will occur .

Watlow EZ-ZONE

®

ST

25

Chapter 2 Install and Wire

Note: Excessive writes to

EEPROM over Modbus can

cause premature EEPROM

failure . The EEPROM is rated

for 1,000,000 writes . See

"Saving Settings to Nonvola-

tile Memory" in Chapter 2,

Install and Wire .

Wiring a Serial EIA-485 Network

Do not route network wires with pow-

er wires. Connect network wires in

daisy-chain fashion when connecting

multiple devices in a network.

A termination resistor may be re-

quired. Place a 120 Ω resistor across

T+/R+ and T-/R- of the last controller

on a network.

Only one protocol per port is avail-

able at a time: either Modbus RTU or

Standard Bus.
Note:

Do not route network wires with power

wires .

- A

+ B

com

98
99

CC
CA
CB

B5
D6
D5

power

- A

+ B

common

power

-

A

+

B

common

power

power

power

power

EZ-ZONE PM

EZ-ZONE ST

ST_ _ -_ _

M _ -_ _ _ _

PLC

98

99

CC

C

A

CB

B5

D6

D5

Power

Supply

fuse

EZ-ZONE RM

98

99

Slot C

power

CZ

CB

CX

CY

CA

CC

- A

+ B

common

- A

+ B

com

- A

+ B

common

power

-

A

+

B

common

power

power

power

EZ-ZONE PM

EZ-ZONE ST

ST_ _ - _ _ A _ -_ _ _ _

98

99

CF

CD

CE

B5

D6

D5

Power

Supply

fuse

EZ-ZONE RM

98

99

Slot C

power

CZ

CE

CX

CY

CD

CF

- A

+ B

common

98
99

CF

CD
CE

B5
D6
D5

98
99

CF

CD
CE

RUI/Gateway

EZKB-_ A _ _- _ _ _ _

A network using Watlow's Standard Bus and an RUI/Gateway .

A network with all devices configured using Modbus RTU .