Watlow EZ-ZONE ST User Manual

Page 51

Advertising
background image

Watlow EZ-ZONE

®

ST

49

Chapter 4 Setup Page

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro DP

Index

Par

ID

RUI/

GTW

Mod-

bus

Data

Type

&

Read/

Write

[`is;a]
[ iS.A]

Alarm (1 to 2)

Source Instance A

Set the instance of the

function selected above.

1 or 2

1

Instance 1

Map 1 Map 2

112

1484

Instance 2

Map 1 Map 2
128

1544

0x6D

(109)

1 to 2

0x12 (18)

22

9018 Inst. 1

1514

Inst. 2

1564

uint
RWES

[`A;hy]
[ A.hy]

Alarm (1 to 2)

Hysteresis

Set the hysteresis for an

alarm. This determines

how far into the safe

region the process value

needs to move before the

alarm can be cleared.

0.001 to 9,999.000°F or units
0.001 to 5,555.000°C

1.0°F or

units

1.0°C

Instance 1

Map 1 Map 2

101

1454

Instance 2

Map 1 Map 2
117

1514

0x6D

(109)

1 to 2

3

24

9003 Inst. 1

1484

Inst. 2

1534

float
RWES

[`A;Lg]
[ A.Lg]

Alarm (1 to 2)

Logic

Select what the output

condition will be during

the alarm state.

[`AL;C]

Close On Alarm (17)

[`AL;o]

Open On Alarm (66)

Close On

Alarm

Instance 1

Map 1 Map 2

104

1458

Instance 2

Map 1 Map 2
120

1518

0x6D

(109)

1 to 2

5

25

9005 Inst. 1

1488

Inst. 2

1538

uint
RWES

[`A;Sd]
[ A.Sd]

Alarm (1 to 2)

Sides

Select which side or sides

will trigger this alarm.

[both]

Both (13)

[high]

High (37)

[LoW]

Low (53)

Both

Instance 1

Map 1 Map 2

103

1456

Instance 2

Map 1 Map 2
119

1516

0x6D

(109)

1 to 2

4

26

9004 Inst. 1

1486

Inst. 2

1536

uint
RWES

[`A;LA]
[ A.LA]

Alarm (1 to 2)

Latching

Turn alarm latching on or

off. A latched alarm has to

be turned off by the user.

[nLAt]

Non-Latching (60)

[`LAt]

Latching (49)

Non-

Latching

Instance 1

Map 1 Map 2

106

1462

Instance 2

Map 1 Map 2
122

1522

0x6D

(109)

1 to 2

7

27

9007 Inst. 1

1492

Inst. 2

1542

uint
RWES

[`A;bL]
[ A.bL]

Alarm (1 to 2)

Blocking

Select when an alarm will

be blocked. After startup

and/or after the set point

changes, the alarm will be

blocked until the process

value enters the normal

range.

[`oFF]

Off (62)

[`Str]

Startup (88)

[StPt]

Set Point (85)

[both]

Both (13)

Off

Instance 1

Map 1 Map 2

107

1464

Instance 2

Map 1 Map 2
123

1524

0x6D

(109)

1 to 2

8

28

9008 Inst. 1

1494

Inst. 2

1544

uint
RWES

[`A;Si]
[ A.Si]

Alarm (1 to 2)

Silencing

Turn alarm silencing on

to allow the user to dis-

able this alarm.

[`oFF]

Off (62)

[``on]

On (63)

Off

Instance 1

Map 1 Map 2

105

1460

Instance 2

Map 1 Map 2
121

1520

0x6D

(109)

1 to 2

6

29

9006 Inst. 1

1490

Inst. 2

1540

uint
RWES

Note:
Some values will be rounded off to fit in the four-character display .

Full values can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E:

EE-

PROM

S:

User

Set