Analog input menu – Watlow EZ-ZONE ST User Manual

Page 42

Advertising
background image

Watlow EZ-ZONE

®

ST

40

Chapter 4 Setup Page

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro DP

Index

Par

ID

RUI/

GTW

Mod-

bus

Data

Type

&

Read/

Write

[``Ai]
[`Set]

Analog Input Menu

[`Sen]
[ SEn]

Analog Input (1 to 2)

Sensor Type

Set the analog sensor type

to match the device wired

to this input.

Note:
There is no open-

sensor detection

for process inputs .

[`oFF]

Off (62)

[``tC]

Thermocouple (95)

[`mu]

Millivolts (56)

[uolT]

Volts dc (104)

[`MA]

Milliamps dc (112)

[r0;1H]

RTD 100 Ω (113)

[r1;0H]

RTD 1,000 Ω (114)

Instance 1

Map 1 Map 2

42

368

Instance 2

Map 1 Map 2
70

458

0x68 (104)

1 to 2

5

3

4005 Inst. 1

368

Inst. 2

528

uint
RWES

[`Lin]
[ Lin]

Analog Input (1 to 2)

Linearization

Set the linearization to

match the thermocouple

wired to this input.

[```J]

J (46)

[```F]

F (30)

[```E]

E (26)

[```d]

D (23)

[```C]

C (15)

[```b]

B (11)

[```t]

T (93)

[```S]

S (84)

[```r]

R (80)

[```n]

N (58)

[```H]

K (48)

J

Instance 1

Map 1 Map 2

43

370

Instance 2

Map 1 Map 2
71

460

0x68 (104)

1 to 2

6

4

4006 Inst. 1

370

Inst. 2

530

uint
RWES

[`Rt;L]
[ rt.L]

Analog Input (1 to 2)

RTD Leads

Set to match the number

of leads on the RTD wired

to this input.

[```2]

2 (1)

[```3]

3 (2)

2

Instance 1

Map 1 Map 2

44

372

Instance 2

Map 1 Map 2
72

462

0x68 (104)

1 to 2

7

- - - -

4007 Inst. 1

372

Inst. 2

532

uint
RWES

[Unit]
[Unit]

Analog Input (1 to 2)

Units

Set the type of units the

sensor will measure.

[`A;tP]

Absolute Temperature

(1540)

[``rh]

Relative Humidity

(1538)

[`Pro]

Process (75)

[PWr]

Power (73)

Process

Instance 1

Map 1 Map 2

- - - -

442

Instance 2

Map 1 Map 2
- - - - 532

0x68 (104)

1 to 2

0x2A (42)

5

4042

- - - - uint

RWES

Note:
Some values will be rounded off to fit in the four-character display .

Full values can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E:

EE-

PROM

S:

User

Set

To go to the Setup Page from the Home Page, press both

the Up ¿ and Down ¯ keys for six seconds. [``Ai] will

appear in the upper display and [`Set] will appear in

the lower display.

• Press the Up ¿ or Down ¯ key to move through

the menus.

• Press the Advance Key

to move to a submenu.

• Press the Up ¿ or Down ¯ key to move through

the submenus.

• Press the Advance Key

to move through the pa-

rameters of the menu or submenu.

• Press the Infinity Key ˆ to move backwards

through the levels: parameter to submenu; sub-

menu to menu; menu to Home Page.

• Press and hold the Infinity Key ˆ for two seconds

to return to the Home Page.

Note:

Avoid continuous writes within loops . Excessive writes to EEPROM

will cause premature EEPROM failure . The EEPROM is rated for

1,000,000 writes . Navigate to Setup Page under the CoM menu and

set prompt Non-volatile Save

[`nU;S]

to No .