Global menu – Watlow EZ-ZONE ST User Manual

Page 54

Advertising
background image

Watlow EZ-ZONE

®

ST

52

Chapter 4 Setup Page

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro DP

Index

Par

ID

RUI/

GTW

Mod-

bus

Data

Type

&

Read/

Write

[gLbL]
[`Set]

Global Menu

[`C_F]
[ C_F]

Global

Display Units

Select which scale to use

for temperature.

[```F]

°F (30)

[```C]

°C (15)

°F

Instance 1
Map 1 Map 2

- - - - 1698

- - - -

110

3005

- - - - uint

RWES

[AC;LF]
[AC.LF]

Global

AC Line Frequency

Set the frequency to the

applied ac line power

source.

[``50]

50 Hz (3)

[``60]

60 Hz (4)

60 Hz

Instance 1
Map 1 Map 2

129

946

0x65 (101)

1

0x22 (34)

- - - -

1034 Inst. 1

886

uint

RWES

[P;typ]

[P.tyP]

Global

Profile StartType

Set the profile startup to

be based on a set point or

a process value.

[StPt]

Set Point (85)

[`Pro]

Process (75)

Set Point

Instance 1
Map 1 Map 2

302

3814

0x7A

(122)

1

8

- - - -

22008 Inst. 1

2914

uint

RWE

[`GSE]

[ gSE]

Global

Guaranteed Soak En-

able

Enables the guaranteed

soak deviation function in

profiles.

[`oFF]

Off (62)

[``on]

On (63)

Off

Instance 1
Map 1 Map 2

299

3810

0x7A

(122)

1

6

- - - -

22006 Inst. 1

2910

uint
RWE

[GSd1]

[gSd1]

Global

Guaranteed Soak De-

viation 1

Set the value of the de-

viation band that will be

used in all profile step

types. The process value

must enter the deviation

band before the step can

proceed.

0.0 to 9,999.000°F or units
0.0 to 5,555.000°C

10.0°F or

units

6.0°C

Instance 1
Map 1 Map 2

300

3812

0x7A

(122)

1

7

- - - -

22007 Inst. 1

2912

float
RWE

No Dis-

play

Global

Ramping Type

Defines whether profiles

will use time or rate

Rate (81)
Time (143)

Time

Instance 1

Map 1 Map 2

- - - - 3874

0x7A

(122)

1

0x26 (38)

- - - -

22038 Inst. 1

- - - -

uint
RWE

[d;prs]
[d.PrS]

Global

Display Pairs

Defines the number of

Display Pairs.

1 to 10

2

Instance 1
Map 1 Map 2

- - - - 1744

- - - -

- - - -

3028

- - - - uint

RWES

[USr;S]
[USr.S]

Global

User Settings Save

Save all of this control-

ler's settings to the se-

lected set.

[SEt1]

User Set 1 (101)

[SEt2]

User Set 2 (102)

[none]

None (61)

None

Instance 1

Map 1 Map 2

17

26

0x(101)

1

0xE (14)

118

1014 Inst. 1

26

uint

RWE

[USr;r]
[USr.r]

Global

User Restore Settings

Replace all of this con-

troller's settings with

another set.

[FCty]

Factory (31)

[none]

None (61)

[SEt1]

User Set 1 (101)

[SEt2]

User Set 2 (102)

None

Instance 1

Map 1 Map 2

16

24

0x65

(101)

1

0xD (13)

117

1013 Inst. 1

24

uint

RWE

Note:
Some values will be rounded off to fit in the four-character display .

Full values can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E:

EE-

PROM

S:

User

Set

Advertising