Conventions used in the menu pages, Watlow standard bus controller address – Watlow EZ-ZONE ST User Manual

Page 29

Advertising
background image

Watlow EZ-ZONE

®

ST

27

Chapter 2 Install and Wire

Watlow Standard Bus Controller Address

The address of an EZ-ZONE ST controller using

Standard Bus exclusively (ST_ _ - _ _ A _ - _ _ _ _ )

ranges from 1 to 16, where up to 16 controllers can be

connected on the Standard Bus network.

DIP Switch

Zone

1

2

3

*4

1

off

off

off

off

2

on

off

off

off

3

off

on

off

off

4

on

on

off

off

5

off

off

on

off

6

on

off

on

off

7

off

on

on

off

8

on

on

on

off

*9

off

off

off

on

*10

on

off

off

on

*11

off

on

off

on

*12

on

on

off

on

*13

off

off

on

on

*14

on

off

on

on

*15

off

on

on

on

*16

on

on

on

on

Conventions Used in the Menu Pages

To better understand the menu pages that follow

review the naming conventions used. When encoun-

tered throughout this document, the word "default"

implies as shipped from the factory. Each page (Op-

erations, Setup, Profile and Factory) and their associ-

ated menus have identical headers defined below:

Header Name

Definition

Display

Visually displayed infor-

mation from the control.

Parameter Name

Describes the function of

the given parameter.

Range

Defines options available

for this prompt, i.e., min/

max values (numerical),

yes/no, etc... (further ex-

planation below).

Default

Values as delivered from

the factory.

Modbus Relative Ad-

dress

Identifies unique address-

es when using either the

Modbus RTU or Modbus

TCP protocols (further ex-

planation below).

CIP (Common Indus-

trial Protocol)

Identifies unique param-

eters using either the

DeviceNet or EtherNet/IP

protocol (further explana-

tion below).

Header Name

Definition

Profibus Index

Identifies unique param-

eters using Profibus DP

protocol (further explana-

tion below).

Parameter ID

Identifies unique param-

eters used with other soft-

ware such as, LabVIEW.

RUI/GTW Modbus

Identifies unique relative

Modbus (RTU or TCP) ad-

dresses when using the

Remote User Interface /

Gateway.

Data Type R/W

uint = Unsigned 16 bit

integer

dint = Signed 32-bit,

long

string = ASCII (8 bits

per character)

float = IEEE 754 32-bit
RWES = Readable

Writable

EEPROM (saved)

User Set (saved)

If Using Optional RUI (Display)
Visual information from the control is displayed to

the observer using a fairly standard 7 segment dis-

play. Due to the use of this technology, several charac-

ters displayed need some interpretation, see the list

below:

[1]

= 1

[0]

= 0

[i]

= i

[r]

= r

[2

= 2

[a]

= A

[j]

= J

[S]

= S

[3]

= 3

[b]

= b

[H]

= K

[t]

= t

[4]

= 4

[c]

, [C] = c

[l]

= L

[U]

= u

[5]

= 5

[d]

= d

[m]

= M

[u]

= v

[6]

= 6

[e]

= E

[n]

= n

[w]

= W

[7]

= 7

[f]

= F

[o]

= o

[y]

= y

[8]

= 8

[g]

= g

[p]

= P

[2]

= Z

[9]

= 9

[h]

= h

[q]

= q

Range
Within this column notice that on occasion there will

be numbers found within parenthesis. This number

represents the enumerated value for that particular

selection. Range selections can be made simply by

writing the enumerated value of choice using any of

the available communications protocols. As an ex-

ample, turn to the Setup Page and look at the Analog

Input [`Ai] menu and then the Sensor Type [Sen]

prompt (instance 1). To turn the sensor off using

Modbus simply write the value of 62 (off) to register

400043 (Map 1) or register 400369 (Map 2) and send

Advertising