Calibration menu – Watlow EZ-ZONE ST User Manual

Page 65

Advertising
background image

Watlow EZ-ZONE

®

ST

63

Chapter 6 Factory Page

Control Module • Factory Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative Ad-

dress

CIP

Class

Instance

Attribute

hex (dec)

Pro DP

Index

Par

ID

RUI/

GTW

Mod-

bus

Data

Type

&

Read/

Write

No Dis-

play

Diagnostics

Hardware ID

Display hardware ID.

17 or 31

Instance 1

Map 1 Map 2

0

0

0x65

(101)

1

1

- - - - 1001 Inst. 1

- - - -

dint

R

No Dis-

play

Diagnostics

Software ID

Display software ID.

0 to 2147483647

- - - -

Instance 1

Map 1 Map 2

2

2

0x65

(101)

1

2

- - - - 1002 Inst. 1

- - - -

dint

R

No Dis-

play

Diagnostics

Device Name

0 or 32

EZ-

ZONE

ST

Instance 1

Map 1 Map 2

0

0

0x65

(101)

1

0x0B(11)

- - - - 1011 Inst. 1

- - - -

string

RWE

No Dis-

play

Diagnostics

Device Status

OK (138)

FAIL (32)

- - - -

Instance 1

Map 1 Map 2

18

30

0x65

(101)

1

0x0A(10)

- - - - 1016 Inst. 1

- - - -

uint

R

[`CAL]
[FCty]

Calibration Menu

[`Mu]
[ Mv]

Calibration (1 to 2)

Electrical Measure-

ment

Read the raw elec-

trical value for this

input in the units

corresponding to the

Sensor Type (Setup

Page, Analog Input

Menu) setting.

-3.4e38 to 3.4e38

Instance 1

Map 1 Map 2

309

400

Instance 2

Map 1 Map 2
311

490

0x68

(104)

1 to 2

0x15

(21)

- - - - 4021 Inst. 1

400

Inst. 2

560

float

R

[ELi;o]
[ELi.o]

Calibration (1 to 2)

Electrical Input

Offset

Change this value to

calibrate the low end

of the input range.

-1,999.000 to 9,999.000

0.0

Instance 1

Map 1 Map 2

47

378

Instance 2

Map 1 Map 2
75

468

0x68

(104)

1 to 2

0xA (10)

- - - - 4010 Inst. 1

378

Inst. 2

538

float

RWES

[ELi;S]
[ELi.S]

Calibration (1 to 2)

Electrical Input

Slope

Adjust this value to

calibrate the slope of

the input value.

-1,999.000 to 9,999.000

1.0

Instance 1

Map 1 Map 2

49

380

Instance 2

Map 1 Map 2
77

470

0x68

(104)

1 to 2

0xB (11)

- - - - 4011 Inst. 1

380

Inst. 2

540

float

RWES

[ELo;o]
[ELo.o]

Calibration (1)

Electrical Output

Offset

Change this value to

calibrate the low end

of the output range.

-1,999.000 to 9,999.000

0.0

Instance 1

Map 1 Map 2

- - - -

788

0x76

(118)

1

5

- - - - 18005 - - - - float

RWES

[ELo;S]
[ELo.S]

Calibration (1)

Electrical Output

Slope

Adjust this value to

calibrate the slope of

the output value.

-1,999.000 to 9,999.000

1.0

Instance 1

Map 1 Map 2

- - - -

790

0x76

(118)

1

6

- - - - 18006 - - - - float

RWES

Note:
Some values will be rounded off to fit in the four-character display . Full values can be
read with another interface .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E: EE-

PROM

S: User

Set

Advertising