Chapter 4 Setup Page

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro DP

Index

Par

ID

RUI/

GTW

Mod-

bus

Data

Type

&

Read/

Write

[`o;tb]
[ o.tb]

Output (1 to 4)

Time Base

Set the time base for

fixed-time-base control.

0.1 to 60.0 seconds (solid-state

relay or switched dc)

5.0 to 60.0 seconds (mechani-

cal relay or no-arc power

control)

0.1 sec.

[SSR &

sw dc]

20.0 sec.

[mech,

relay, no-

arc]

Instance 1

Map 1 Map 2

132

944

[Map1 Offset

+ 13]

[Map2 Offset

+ 30]

0x6A

(106)

1 to 4

3

86

6003 Inst. 1

884

Offset

+ 30

float
RWES

[`o;Lo]
[ o.Lo]

Output (1 to 4)

Low Power Scale

The power output will

never be less than the

value specified and will

represent the value at

which output scaling

begins.

0.0 to 100.0%

0.0%

Instance 1

Map 1 Map 2

139

956

[Map1 Offset

+ 13]

[Map2 Offset

+ 30]

0x6A

(106)

1 to 4

9

87

6009 Inst. 1

896

Offset

+ 30

float
RWES

[`o;hi]
[ o.hi]

Output (1 to 4)

High Power Scale

The power output will

never be greater than

the value specified and

will represent the value

at which output scaling

stops.

0.0 to 100.0%

100.0%

Instance 1

Map 1 Map 2

141

958

[Map1 Offset

+ 13]

[Map2 Offset

+ 30]

0x6A

(106)

1 to 4

0xA (10)

88

6010 Inst. 1

898

Offset

+ 30

float
RWES

[``Fn]
[ Fn]

Output (1)

Function

Select what function will

drive this output.

[`oFF]

Off (62)

[heat]

Heat, Control Loop

(36)

[Cool]

Cool, Control Loop

(20))

off

Instance 1

Map 1 Map 2

- - - -

782

0x6A

(118)

1

2

- - - -

18002 - - - - uint

RWES

[ss;ti]
[SS.ti]

Output (1)

Soft Start Time

Set the time (in seconds)

it takes to achieve 100%

power

0.0 to 1000.0 seconds

0

Instance 1

Map 1 Map 2

- - - -

820

0x76 (118)

1

0x15 (21)

- - - -

18021 - - - - float

RWES

[Alm]
[`Set]

Alarm Menu

[`A;ty]
[ A.ty]

Alarm (1 to 2)

Type

Select whether the alarm

trigger is a fixed value or

will track the set point.

[`oFF]

Off (62)

[PR;AL]

Process Alarm (76)

[dE;AL]

Deviation Alarm (24)

Off

Instance 1

Map 1 Map 2

110

1478

Instance 2

Map 1 Map 2
126

1538

0x6D

(109)

1 to 2

0xF (15)

20

9015 Inst. 1

1508

Inst. 2

1558

uint
RWES

[`sr;a]
[ Sr.A]

Alarm (1 to 2)

Source Function A

Select what will trigger

this alarm.

[``Ai]

Analog Input (142)

[CUrr]

Current (22)

[PWr]

Power, Control Loop

(73)

Instance 1

Map 1 Map 2

111

1482

Instance 2

Map 1 Map 2
127

1542

0x6D

(109)

1 to 2

0x11 (17)

21

9017 Inst. 1

1512

Inst. 2

1562

uint
RWES