Watlow EZ-ZONE ST User Manual

Page 45

Advertising
background image

Watlow EZ-ZONE

®

ST

43

Chapter 4 Setup Page

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro DP

Index

Par

ID

RUI/

GTW

Mod-

bus

Data

Type

&

Read/

Write

[`o;tb]
[ o.tb]

Digital Output (5 or 6)

Time Base

Set the time base for

fixed-time-base control.

0.1 for Fast and Bi-Directional

outputs, 5.0 for Slow out-

puts] to 60

Instance 5

Map 1 Map 2

171

1064

Instance 6

Map 1 Map 2
184

1094

0x6A

(106)

5 to 6

3

86

6003 Inst. 5

1004

Inst. 6

1034

float

RWES

[`o;Lo]
[ o.Lo]

Digital Output (5 or 6)

Low Power Scale

The power output will

never be less than the

value specified and will

represent the value at

which output scaling

begins.

0.0 to 100.0

0.0

Instance 5

Map 1 Map 2

178

1076

Instance 6

Map 1 Map 2
191

1106

0x6A

(106)

5 to 6

9

87

6009 Inst. 5

1016

Inst. 6

1046

float
RWES

[`o;hi]
[ o.hi]

Digital Output (5 or 6)

High Power Scale

The power output will

never be greater than

the value specified and

will represent the value

at which output scaling

stops.

0.0 to 100.0

100.0

Instance 5

Map 1 Map 2

180

1078

Instance 6

Map 1 Map 2
193

1108

0x6A

(106)

5 to 6

0xA (10)

88

6010 Inst. 5

1018

Inst. 6

1048

float
RWES

[`leu]
[ LEv]

Digital Input (5 or 6)

Level

Select which action will

be interpreted as a true

state.

[high]

High (37)

[LoW]

Low (53)

High

Instance 5
Map 1 Map 2

264

1290

Instance 6

Map 1 Map 2
268

1310

0x6E

(110)

5 to 6

1

137

10001 Inst. 5

1400

Inst. 6

1420

uint

RW

[``Fn]
[ Fn]

Digital Input (5 or 6)

Action Function

Select the function that

will be triggered by a true

state.

[none]

None (61)

[lmr]

Limit Reset (82)

[P;StS]

Profile Start/Stop

(208)

[ProF]

Start Profile (196)

[P;hoL]

Profile Hold/Resume

(207)

[P;diS]

Profile Disable (206)

[`t;dA]

TRU-TUNE+™ Dis-

able (219)

[`off]

Switch Loop Off (62)

[MAn]

Manual (54)

[tUnE]

Tune (98)

[idLE]

Idle Set Point (107)

[`F;AL]

Force Alarm to Occur

(218)

[`AoF]

Control Loops Off and

Alarms to Non-alarm State

(220)

[`SiL]

Silence Alarms (108)

[ALM]

Alarm (6)

[USr;r]

User Settings Restore

(227)

Instance 5
Map 1 Map 2

266

1294

Instance 6

Map 1 Map 2
270

1314

0x6E

(110)

5 to 6

3

138

10003 Inst. 5

1404

Inst. 6

1424

uint

RWES

Note:
Some values will be rounded off to fit in the four-character display .

Full values can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E:

EE-

PROM

S:

User

Set

Advertising