Watlow EZ-ZONE

®

ST

61

Chapter 6 Factory Page

Control Module • Factory Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative Ad-

dress

CIP

Class

Instance

Attribute

hex (dec)

Pro DP

Index

Par

ID

RUI/

GTW

Mod-

bus

Data

Type

&

Read/

Write

[LoC;P]
[LoC.P]

Security Setting

Profiling Page

Change the security

level of the Profiling

Page.

1 to 3

3

Instance 1

Map 1 Map 2

- - - - 1704

- - - -

- - - - 3008 - - - - uint

RWE

[pas;e]
[LoC.P]

Security Setting

Password Enable

Turn security fea-

tures on or off.

[`off]

Off

[``on]

On

Off

Instance 1

Map 1 Map 2

- - - - - - - -

- - - -

- - - - 3009 - - - - uint

RWE

[rLoC]
[rLoC]

Security Setting

Read Lock

Set the read security

clearance level. The

user can access the

selected level and all

lower levels.

If the Set Lockout Se-

curity level is higher

than the Read Lock-

out Security, the Read

Lockout Security

level takes priority.

1 to 5

5

Instance 1

Map 1 Map 2

- - - - 1708

- - - -

- - - - 3010 - - - - uint

RWE

[SLoC]
[SLoC]

Security Setting

Write Security

Set the write security

clearance level. The

user can access the

selected level and all

lower levels.

If the Set Lockout Se-

curity level is higher

than the Read Lock-

out Security, the Read

Lockout Security

level takes priority.

0 to 5

5

Instance 1

Map 1 Map 2

- - - - 1710

- - - -

- - - - 3011 - - - - uint

RWE

[loC;l]
[LoC.L]

Security Setting

Locked Access Level

Determines user level

menu visibility when

security is enabled.

See Features section

under Password Se-

curity.

1 to 5

5

Instance 1

Map 1 Map 2

- - - - - - - -

- - - -

- - - - 3016 - - - - uint

RWE

[roll]
[roLL]

Security Setting

Rolling Password

When power is cycled

a new Public Key will

be displayed.

[`off]

Off

[``on]

On

Off

Instance 1

Map 1 Map 2

- - - - - - - -

- - - -

- - - - 3019 - - - - uint

RWE

[pas;u]
[PAS.u]

Security Setting

User Password

Used to acquire ac-

cess to menus made

available through the

Locked Access Level

setting.

10 to 999

63

Instance 1

Map 1 Map 2

- - - - - - - -

- - - -

- - - - 3017 - - - - uint

RWE

Note:
Some values will be rounded off to fit in the four-character display . Full values can be
read with another interface .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E: EE-

PROM

S: User

Set

Advertising