Declaration of conformity, Series ez-zone, St tower – Watlow EZ-ZONE ST User Manual

Page 95: Watlow, Iso 9001

Advertising
background image

Watlow EZ-ZONE

®

ST

93

Appendix

Declaration of Conformity

CE DOC EZ-ZONE ST-01-10

Page 1 of 2

Series EZ-ZONE

®

ST Tower

WATLOW

an

ISO 9001

approved facility since 1996.

1241 Bundy Blvd.

Winona, MN 55987 USA

Declares that the following product:
Designation:

Series EZ-ZONE

®

ST Tower

Model Numbers:

ST, followed by K, B, P, E, H, D, J or C, followed by A, L or B, followed

by A, B or F, followed by L, H, 1, 2 or 3, followed by any letter or

number, followed by A – H, J – N, P, R, S or T, followed by A, B, C, D,

E or F followed by any three numbers or letters.

Classification:

Temperature control, Installation Category II, Pollution degree 2, IP20

Rated Voltage and Frequency: Control 100 to 240 V~ ac or 24 to 28 V� ac or dc (ac = 50/60 Hz)

Load 24 to 240 V~ ac

or 48 to 600 V~ ac zero cross, or

Load 100 to 240 V~ ac

or 260 to 600 V~ ac phase angle

3

.

Rated Power Consumption:

Control 12 VA, Control with Contactor 50 VA, Control with external

contactor 140 VA. Load Current 25, 40 or 75A depending upon SSR

and heatsink used. (see derating curve)

Meets the essential requirements of the following European Union Directives by using the relevant

standards show below to indicate compliance.

2004/108/EC Electromagnetic Compatibility Directive

EN 61326-1

2006

Electrical equipment for measurement, control and laboratory

use – EMC requirements (Industrial Immunity, Class A

Emissions

1

). Not for use in a Class B environment without

additional filtering.

EN 61000-4-2

1996 +A1,A2:2001 Electrostatic Discharge Immunity

EN 61000-4-3

2006

Radiated Field Immunity

EN 61000-4-4

2004

Electrical Fast-Transient / Burst Immunity

EN 61000-4-5

2006

Surge Immunity

EN 61000-4-6

1996

+A1,A2,A3:2005

Conducted Immunity

EN 61000-4-8

1994 +A1, 2001

Magnetic Field Immunity

EN 61000-4-11 2004

Voltage Dips, Short Interruptions and Voltage Variations Immunity

EN 61000-3-2

4

2006

Harmonic Current Emissions

EN 61000-3-3

2

2005

Voltage Fluctuations and Flicker

SEMI F47

2000

Specification for Semiconductor Sag Immunity Figure R1-1

1

NOTE 1: Use of an external filter is required to comply with conducted emissions limits for load

terminals. For 230 Vac or less, use Watlow P/N 14-0019 or Crydom P/N 1F25 filters. For voltages

up to 440 Vac use Watlow P/N 14-0020 or Crydom P/N 3F20 filters. A Line Impedance Stabilization

Network (LISN) was used for conducted emissions measurements.

2

NOTE 2: To comply with flicker requirements cycle time may need to be greater than 175

seconds if Load Power is ≤ 16A to comply with standard, or the maximum source impedance

needs to be determined. Source impedance shall meet EN 61000-3-11 requirements for load

currents > 16A. Control module power complies with 61000-3-3 requirements.