Chapter 4 Setup Page

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro DP

Index

Par

ID

RUI/

GTW

Mod-

bus

Data

Type

&

Read/

Write

[`h;SP]
[ h.SP]

Control Loop (1)

Set Point Closed Limit

High

Set the high end of the set

point range.

-1,999.000 to 9,999.000°F or

units

-1,128.000 to 5,537.000°C

9,999°F or

units

5,537°C

Instance 1

Map 1 Map 2

197

1896

0x6B

(107)

1

4

53

7004 Inst. 1

2166

float
RWES

[SP;Lo]
[SP.Lo]

Control Loop (1)

Set Point Open Limit

Low

Set the minimum value

of the open-loop set point

range.

-100.0 to 100.0%

-100

Instance 1

Map 1 Map 2

199

1898

0x6B

(107)

1

5

54

7005 Inst. 1

2168

float
RWES

[SP;hi]
[SP.hi]

Control Loop (1)

Set Point Open Limit

High

Set the maximum value

of the open-loop set point

range.

-100.0 to 100.0%

100

Instance 1

Map 1 Map 2

201

1900

0x6B

(107)

1

6

55

7006 Inst. 1

2170

float
RWES

[otpt]
[`Set]

Output Menu

[``Fn]
[ Fn]

Output (1 to 4)

Function

Select what function will

drive this output.

[`oFF]

Off (62)

[ALM]

Alarm (6)

[heat]

Heat, Control Loop

(36)

[Cool]

Cool, Control Loop (20)

[LiM]

Limit (126)

[Ent;A]

Profile Event Out A

(233)

[Ent;b]

Profile Event Out B

(234)

off

Instance 1

Map 1 Map 2

134

948

[Map1 Offset

+ 13]

[Map2 Offset

+ 30]

0x6A

(106)

1 to 4

5

83

6005 Inst. 1

888

Offset

+ 30

uint
RWES

[``Fi]
[ Fi]

Output (1 to 4)

Function Instance

Set the instance of the

function selected above.

1 to 4

1

Instance 1

Map 1 Map 2

135

950

[Map1 Offset

+ 13]

[Map2 Offset

+ 30]

0x6A

(106)

1 to 4

6

84

6006 Inst. 1

890

Offset

+ 30

uint
RWES

[`o;Ct]
[ o.Ct]

Output (1 to 4)

Control

Set the output control

type. This parameter

is only used with PID

control, but can be set

anytime.

[`Ftb]

Fixed Time Base (34)

[`utb]

Variable Time Base

(103)

Fixed

Time

Base

Instance 1

Map 1 Map 2

131

942

[Map1 Offset

+ 13]

[Map2 Offset

+ 30]

0x6A

(106)

1 to 4

2

85

6002 Inst. 1

882

Offset

+ 30

uint
RWES

Note:
Some values will be rounded off to fit in the four-character display .

Full values can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .