Chapter 1 Overview

Ó

WARNING: When the controller is powered up, the outputs

may turn on .

Note:

A current error can be sent to the RUI (Remote User

Interface) soft error display by enabling Current

Reading [`CU;r] in the Setup Page.

Note:

Number of inputs and outputs and various combinations of the same will vary

depending upon part number; see ordering matrix for more detail.

High

Current

Power

Digital Input 5 & 6

(optional) DC voltage, Dry Contact

Limit Controller

Board

(optional)

Input

Functions

Output

Functions

- None

- Limit reset

- Profile start/stop

- Profile start

- Profile hold/resume

- Profile disable

- TRU-TUNE+

®

disable

- Switch Control Loop Off

- Manual mode

- Tune

- Idle set point

- Force alarm

- Loop & alarms off

- Silence alarm

- Alarm clear, request

- Restore user settings

Analog Input 1

none, Thermocouple, RTD (100Ω,

1kΩ), Process (V, mV, mA)

PID

Controller

(Optional -

Ramp/Soak max 4

files, 40 steps)

Input Sensor

off, heat, cool

alarm, event

Limit

off, heat, cool,

alarm, event, limit

Standard Bus

Zone Address

1 - 16

Supervisory &

Power Board

Modbus

Address 1 - 247

EIA-485 Communication

Standard Bus

(optional Modbus RTU)

*RUI, EZ-ZONE

Controllers, PLC, PC

or HMI

Input Sensor

If Limit, this output must

be Limit

Output 2

5A Mechanical Relay (form A), or

0.5A Solid State Relay (form A)

Output 1

Solid State Relay (form A)

off, heat, cool

Analog Input 2

none, Thermocouple, RTD (100Ω,

1kΩ), Process (V, mV, mA)

Output 3

5A Mechanical Relay (form C)

Output 4

5A Mechanical Relay (form A)

Digital Output 5 & 6

(optional) none, switched dc

off, heat, cool,

event, limit, alarm

Contactor

(optional)

Current Sensor

(optional)

* EZ-ZONE Remote User Interface (RUI)

EZ-ZONE

®

ST System Diagram