Chapter 8: appendix, Troubleshooting – Watlow EZ-ZONE ST User Manual

Page 81

Advertising
background image

Watlow EZ-ZONE

®

ST

79

Appendix

Chapter 8: Appendix

Troubleshooting

Indication

Description

Possible Cause(s)

Corrective Action

Alarm won’t clear or

reset

Alarm will not clear or reset

with keypad or digital input

• Alarm latching is active

• Alarm set to incorrect output

• Alarm is set to incorrect source

• Sensor input is out of alarm set point

range

• Alarm set point is incorrect

• Alarm is set to incorrect type

• Digital input function is incorrect

• Reset alarm when process is within

range or disable latching.

• Set output to correct alarm source

instance.

• Set alarm source to correct input in-

stance.

• Correct cause of sensor input out of

alarm range.

• Set alarm set point to correct trip

point.

• Set alarm to correct type: process, de-

viation or power.

• Set digital input function and source

instance.

Alarm won’t occur

Alarm will not activate output • Alarm silencing is active

• Alarm blocking is active
• Alarm is set to incorrect output

• Alarm is set to incorrect source

• Alarm set point is incorrect

• Alarm is set to incorrect type

• Disable alarm silencing, if required.
• Disable alarm blocking, if required.
• Set output to correct alarm source

instance.

• Set alarm source to correct input in-

stance.

• Set alarm set point to correct trip

point.

• Set alarm to correct type: process, de-

viation or power.

[AL`1]

Alarm Error

[AL`2]

Alarm state cannot be deter-

mined due to lack of sensor

input

• Sensor improperly wired or open
• Incorrect setting of sensor type
• Calibration corrupt

• Correct wiring or replace sensor.
• Match setting to sensor used.
• Check calibration of controller.

Sensor input below low alarm

set point

• Temperature is less than alarm set

point

• Alarm is set to latching and an alarm

occurred in the past

• Incorrect alarm set point
• Incorrect alarm source

• Check cause of under temperature.

• Clear latched alarm.

• Establish correct alarm set point.
• Set alarm source to proper setting.

Sensor input above high

alarm set point

• Temperature is greater than alarm

set point

• Alarm is set to latching and an alarm

occurred in the past

• Incorrect alarm set point
• Incorrect alarm source

• Check cause of over temperature.

• Clear latched alarm.

• Establish correct alarm set point.
• Set alarm source to proper setting.

[Er;i1]

Error Input

[Er;i2]

Sensor does not provide a

valid signal to controller

• Sensor improperly wired or open
• Incorrect setting of sensor type
• Calibration corrupt

• Correct wiring or replace sensor.
• Match setting to sensor used.
• Check calibration of controller.

Limit won’t clear or

reset

Limit will not clear or reset

with keypad or digital input

• Sensor input is out of limit set point

range

• Limit set point is incorrect
• Digital input function is incorrect

• Correct cause of sensor input out of

limit range.

• Set limit set point to correct trip point.
• Set digital input function and source

instance.

[LiM]

Limit Error

Limit state cannot be deter-

mined due to lack of sensor

input, limit will trip

• Sensor improperly wired or open
• Incorrect setting of sensor type
• Calibration corrupt

• Correct wiring or replace sensor.
• Match setting to sensor used.
• Check calibration of controller.

8