Section 1: product description, 1 product features, Product features – Fire-Lite ECC-50/100E Emergency Command Center User Manual

Page 12

Advertising
background image

12

Emergency Command Center Manual —

P/N LS10001-000FL-E:A 4/10/2013

Section 1: Product Description

The Fire•Lite Emergency Command Center ECC-50/100 is a single channel, 50 watt, 25 V

RMS

,

emergency voice evacuation panel that may be used for fire applications, mass notification applica-

tions, or both. The ECC-50/100 comes standard with one speaker circuit. The panel provides the

ability to record fourteen field programmable messages (up to 60 seconds each) with an integral

microphone or from an external audio source. An integral power supply with battery charger sup-

plies operational power. A 50 watt audio amplifier is built into each panel. An optional second 50

watt amplifier (ECC-50W-25/70V) is also available for backup purposes or to provide an additional

50 watts. The backup amplifier is available in either 25 volts or 70 volts depending on which appli-

cation is necessary.
Automatic activation of the ECC-50/100 by an FACP is possible via eight Command Input Circuits

(CMD) or via the ACS/ANN Bus serial communications link from the MS-9600(UD)LS and

MS-9200UDLS FACPs.
Two Command Input Circuits can be independently field programmed for activation by an FACP

Notification Appliance Circuit reverse polarity or by closure of a supervised normally open contact

and six Command Input Circuits activate on contact closure. CMD 1 and CMD 2 provide terminals

for NAC input and output to allow installation of the audio panel anywhere along the NAC circuit

being used to activate it.
If the message generator fails, the system automatically reverts to a backup tone generator.
Power is fed independently to each amplifier so that a short circuit in one amplifier will not shut

down the other. Full output power of 50 watts per amplifier is generated while in a low battery con-

dition. Power is not diminished when the optional 70 V

RMS

transformer module is installed. Audio

is amplified utilizing modern integrated circuits as opposed to transformer technology. This pro-

vides for very low signal distortion for crystal clear audio.
Primary applications for the audio panels include protecting structures such as military facilities,

restaurants, schools, auditoriums, places of worship, buildings with occupancies over 50, etc. The

ECC-50/100 is designed to interface directly to addressable or conventional (CMD inputs 1-8) fire

alarm control panels or can be used with the ECC-50/125DA panel to distribute audio in systems

that require more than 100 watts.

1.1 Product Features

Modular design for maximum system flexibility and easy expansion

Removable terminal blocks for ease of servicing and module replacement

50 watts of 25 V

RMS

audio power (expandable to 100 watts)

2 amp Notification Appliance Circuit (NAC) output, sync generator, or follower for protocols:
– System Sensor
– Wheelock
– Gentex

Optional 70.7 V

RMS

conversion transformer available for the primary amplifier (note that

speaker wiring continues to be supervised in standby, alarm and when background music is

playing with this optional transformer installed)

Eight Command Input Circuits to activate messages 1 to 8:
– CMD1 and CMD2 are field selectable to be activated from 12 or 24 VDC Notification

Appliance Circuits (reverse polarity) or contact closures

– CMD3-CMD8 are activated by contact closures

Speaker Circuits
– single Style Y (Class B) or Style Z (Class A) speaker circuit

Advertising
This manual is related to the following products: