Section 3: programming, To section 3) – Fire-Lite ECC-50/100E Emergency Command Center User Manual

Page 58

Advertising
background image

58

Emergency Command Center Manual —

P/N LS10001-000FL-E:A 4/10/2013

Section 3: Programming

All ECC programming is done using the built-in web-based programming utility. It is recom-

mended that tone selection, message repeat cycles and background music options be reviewed and

approved by the local AHJ.
To start programming, use a standard CAT5e Ethernet cable to connect a personal computer’s IP

port (Ethernet) to the IP port (Ethernet) J2 on the main control board (right side of the board). Set

the computer’s local area network connection address as follows:

IP address: 169.254.3.5

Subnet mask: 255.255.0.0

Activate the PC’s web browser (Microsoft Internet Explorer or Mozilla Firefox). Enter the follow-

ing in the browser’s navigation bar:

http://169.254.3.3
The main menu will display and allow further menu navigation.

Security and Data Protection:
NO ENCRYPTION EMPLOYED

Communication Security:
– a. Level 1

Stored Data Security:
– a. Level 0

Access Control Security:
– a. Level 1

Physical Security:
– a. Level 1

Audit Control: not provided

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION

AND OTHER INVOLVED PARTIES

This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard
for Control Units and Accessories for Fire Alarm Systems, UL 864, and in the standard for Communication and Control Units for
Mass Notification Systems, UL 2572, certain programming features or options must be limited to specific values or not used at all
as indicated below:

Program feature
or option

Permitted in

UL 864/UL 2572?

(Y/N)

Possible settings

Settings permitted in
UL 864/UL 2572

AC Loss Delay

Y

AC Loss Delay = 0, 2 (factory default), 6, 12, or 23 hours
Refer to “AC Loss Delay” on page 60.

AC Loss Delay = 2 hours

24 Hour Resound

Y

24 Hour Resound = Enabled
24 Hour Resound = Disabled
Refer to “24 Hour Resound” on page 60

24 Hour Resound
Enabled

NOTE: Be sure to record the computer’s original addresses so they can be restored when ECC
programming is complete.

NOTE: All screen shots reflect default programming.

Advertising
This manual is related to the following products: