Fire-Lite ECC-50/100E Emergency Command Center User Manual

Page 14

Advertising
background image

14

Emergency Command Center Manual —

P/N LS10001-000FL-E:A 4/10/2013

Product Description

Input/Output Circuit Specifications

Battery (lead acid only) - J7

Maximum Charging Circuit: Normal Flat Charge - 27.3V @ 2.8 amps

Maximum Charger Capacity: 26 Amp Hour battery. (ECC cabinet holds max. 18 Amp Hour Bat-

tery.

Minimum Battery Size: 12 Amp Hour

MNS Active Relay - TB1

Form-C relay contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive),

Form-C Trouble Relay - TB2

Form-C relay contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amp @ 30 VAC (resistive).

AC Loss Relay - TB3

Form-C relay contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive),

NAC Output - TB19, Terminals 1 (B+), 2 (A+), 3 (A-), & 4 (B-)

One (1) Style Y (Class B) or Style Z (Class A) circuit

Power-limited circuitry (Class 2), supervised

Nominal operating voltage: 24 VDC

Maximum signaling current for special application power: 2.0 amps

Maximum signaling current for regulated power: 200mA

Current limit: fuseless, electronic, power-limited

Maximum wiring impedance: 1 

End-Of-Line Resistor: 4.7 K, ½ watt, (P/N 71252) required for Style Y (Class B) operation

Refer to the Device Compatibility Document for listed compatible devices.

NAC Follower - TB18, Terminals 3 (IN+), 4 (IN-), 1 (OUT+) & 2 (OUT-)

Connections for FACP NAC synchronization trigger signal

Output terminals: pass-through to other system components

Trigger input voltage: 9 to 32 VDC, 24 VDC rated

Input current draw in Alarm condition: 10 mA at rated voltage

Special Application Power (Aux. Power) - TB17 Terminals 1(+) & 2(-)

Up to 500 mA @ 24 VDC of special application power is available for powering addressable mod-

ules and associated End-of-Line power supervision relays.

Power-limited (Class 2) circuitry. Refer to the Device Compatibility Document for a list of compat-

ible devices.

Speaker Volume Control Override - TB23, Terminals 1 (B+), 2 (A+), 3 (A-), & 4 (B-)

Style Y (Class B) or Style Z (Class A) circuit

Special Application power

Power-limited (Class 2) circuitry, supervised

Nominal operating voltage: 24 VDC

Maximum signaling current: 0.25 amps

Current limit: fuseless, electronic, power-limited

End-Of-Line Resistor: 4.7 K, ½ watt, (P/N 71252) required for Style Y (Class B) operation

Speaker Circuits

Primary Speaker Circuit - TB20,

Terminals 1(+) & 2(-) Style Y (Class B), 4(+) & 5(-) Style Z

(Class A), 3 Shield (Standby and Alarm Polarity Shown) on main control board

Secondary Speaker Circuit (with optional amplifier only) - TB21,

Terminals 1(+) & 2(-)

Style Y (Class B), 4(+) & 5(-) Style Z (Class A), 3 Shield (Standby and Alarm Polarity Shown) on

main control board