Emergency Command Center Manual —

P/N LS10001-000FL-E:A 4/10/2013

Programming

Programmed Activation by FACP

4. When using the ACS communication protocol, a monitor module must be wired to TB1 of the

ECC-50/100. Type Code, “MNS EVENT” must be assigned to the monitor module for mass

notification event monitoring. See Figure 2.21 for wiring information.

FACP Programming

The MS-9600(UD)LS and MS-9200UDLS FACPs must be programmed to operate with the ECC-

50/100. The following table summarizes the steps involved in programming the FACPs.

Note 1:

Zone 32 is assigned to all speaker circuits. If an addressable device programmed to Zone

32 is activated, the message programmed to Zone 32 will be generated to all speaker circuits. The

exception is when one or more devices programmed to Zones 33 through 40 is also activated. If the

newly activated zone is programmed to a message with a higher priority then Zone 32, the higher

priority message will be generated to all circuits.

Note 2:

Messages have a priority scheme with Message 1 having the highest priority and Message

14 having the lowest priority. For example, If an addressable device activates a speaker circuit pro-

grammed to generate Message 14, that message will be generated over the selected speaker zone.

If later, another device activates a speaker circuit programmed to generate Message 3, Message 3

has a higher priority then Message 5 and will therefore be generated over both activated speaker

zones. The highest priority message will always be generated over all activated speaker circuits.

Note 3:

It is important to note that Message 1 is assigned to Zone 00 (General Alarm) as a default.

A message, however, will not be generated over the speaker circuits unless one of the following

programming steps is completed:

For General Alarm applications, all input points must have an audio zone assigned to it:

Z32 to activate all audio zones

OR

Z33 to Z56 for specific audio zone control

For non-General Alarm applications where input devices and/or messages are mapped to spe-

cific zones, Message 1 must be removed from Zone 00 programming.

FACP Message Assignment - Speaker Specific

The ECC-50/100 has the capability of generating up to fourteen different messages. Any one of the

fourteen messages can be programmed to each of the speaker circuit zones Z32 through Z56.

Example 1:

If an addressable device programmed to Zone 35 is activated and no other devices are

active, the message programmed for Zone 35 will be generated over speaker circuit 3.

Example 2:

If an addressable device (address 09 in example below) programmed to Zone 35 is

activated and a second addressable device (address 15 in example below) programmed to Zone 36

is activated, the highest priority message programmed to either Zone 35 or Zone 36 (Message 3 in

1.

Enable the ACS or ANN-BUS annunciator at FACP

refer to FACP manual Option Module Programming

2.

Assign zone(s) to each SLC input device at FACP

refer to FACP manual Point Programming

3.

Program message to be generated over each speaker circuit at FACP

refer to Message Assignment in following section

4.

Activate individual SLC devices to ensure proper programming

compare to desired programming

Table 3.3 FACP Programming Steps

Addressable Pull Station

Programmed to

Message 3

Zone 35

activate

Speaker Circuit 3

e

c

c

e

x

1

.w

m

f