Emergency Command Center Manual —

P/N LS10001-000FL-E:A 4/10/2013

31

Operating Power

Installation

2.3.2 Secondary Power Source (Batteries)

The batteries must be sealed lead acid type. Before con-

necting the batteries to the FACP, make certain that the

interconnect cable between the batteries is not connected.

Do not connect the interconnect cable until the system is

completely installed.

Observe polarity when connecting the batteries. Connect the battery cable to J7 on the main control

board, using the plug-in connector and cable provided. The battery charger is current-limited and

capable of recharging sealed lead acid type batteries (See Figure 2.7 for battery orientation). The

charger shuts off when the system is in alarm. See page 93 for calculation of the correct battery rat-

ing.

-

-

+

+

Interconnect
Cable

!

WARNING: RISK OF PERSONAL INJURY
BATTERY CONTAINS SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN
AND EYES AND CAN DESTROY FABRICS. IF CONTACT IS MADE WITH SULFURIC ACID,
IMMEDIATELY FLUSH THE SKIN OR EYES WITH WATER FOR 15 MINUTES AND SEEK IMME-
DIATE MEDICAL ATTENTION.

Figure 2.7 Operating Power Connections

e

c

c

p

o

w

e

r.

w

m

f

VAC

Hot (black)

Ground (green)

Neutral (white)

Connect Earth

Ground wire to

ground stud with

grounding cable

black (-)

red (+)

18 AH

battery

18 AH

battery