Main Menu - User Programming

Programming

Primary Amp 70 VAC This field has no effect on programming and is used for informational
purposes only.

The system can be converted from 25V to 70V by installing the ECC-XRM-70V. If

this transformer has been installed, be sure that SW5 on the main control board has been set to

“70V” operation. Use this field to record the amplifier’s settings.

Secondary Amp 70 VAC This field has no effect on programming and is used for informational
purposes only.

When the ECC-XRM-70V has been installed and a secondary amplified is required,

model number ECC-50W-70V must be used. Use this field to record which model has been

installed in the system.

External Audio Input

If there is a permanent connection to TB5 on the display board, select

whether the external audio input will function as Background Music or External Paging - Night
Ring

. See Section 4.4.15 for more information.

IP Address

The default IP address of 169.254.3.3 can be changed to another address with num-

bers from 0-255. Changing the IP address is suggested for a higher level of security on the sys-

tem’s programming. This number should be written down and stored in a safe location.

Identification

Enter a label for this ECC system. Up to 80 character may be entered.

NAC Options

NAC Type

The programmer can select the notification appliance coding or strobe synchroniza-

tion by selecting the corresponding drop-down box. The selections are:

Steady - a continuous output with no coding

Follow Input - follows the signal on the NAC Follower input - TB18, for a fire evacuation-only

system.

If synchronized strobes were selected as the type of device installed, the type of synchronization

must be selected in this option. Select System Sensor, Gentex, or Wheelock.
To ensure proper strobe and circuit operation, there is also a limit to the number of strobes that can

be attached to each circuit. Following is a list of the strobes that have been tested with the ECC and

the maximum number that can be connected to each NAC. Make sure that the NAC maximum cur-

rent is not exceeded.

Aux Power

Selects whether this power is Constant or Resettable use from TB17.

Speaker Volume Control NAC

If the Cooper Wheelock SP-SVC module is installed on TB23

of the main control board, allowing manual volume setting for telephone paging and background

music for a specific speaker or speaker zone, select Enabled.

Strobe Manufacturer

Maximum Number of Strobes

System Sensor

31

Wheelock

34

Gentex

26

Table 3.1 Maximum Number of Strobes by Manufacturer