Emergency Command Center Manual —

P/N LS10001-000FL-E:A 4/10/2013

Installation

UL Power-limited Wiring Requirements

2.12 UL Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All

power-limited circuit wiring must remain at least 0.25" away from any nonpower-limited circuit

wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must enter and exit the

cabinet through different knockouts and/or conduits. A typical wiring diagram for the ECC-50/100

with two speaker circuits is shown below.

Figure 2.30 Typical Wiring Diagram for UL Power-limited Requirements

Power-limited Circuits

(Class 2)

e

c

c

u

lp

w

r.

w

m

f

Power-limited Circuits

(Class 2)

Power-limited

Circuits

(Class 2)

AC Power

Nonpower-

limited Circuit

Power-limited

Circuits

(Class 2)

Power-limited

Circuits

(Class 2)

to batteries

nonpower-

limited circuit

Power-limited

Circuits

(Class 2)

NOTE: Use of the 70V transformer makes all power-limited circuits Class 3.