Appendix B: Wiring Requirements

Connecting external system accessories to the ECC-50/100 main circuits must be carefully consid-

ered to ensure proper operation. It is important to use the correct type of wire, wire gauge and wire

run length per each circuit. Refer to the following table to specify wire requirements and limita-

tions.

NOTE: If an SLC loop is to be run in conduit with ECC-50/100 Notification Appliance Circuits,
the risk of encountering problems can be greatly reduced by using twisted, shielded cable on the
SLC and NACs.

Circuit Type

Wire Type & Limitations

Maximum Distance (feet)

Wire Guage (terminals support)

CMD1-CMD2
TB4, TB5: polarity reversal

untwisted/unshielded,
twisted/shielded, see note

1

depends on trigger circuit,
9-32 VDC, 1.6 mA

12-18 AWG

CMD1-CMD2
TB4, TB5: contact closure

untwisted/unshielded,
twisted/shielded, see note

1

max loop impedance 200 ohms

12-18 AWG

CMD3-CMD8
TB6-TB8: contact closure

untwisted/unshielded,
twisted/shielded, see note

1

max loop impedance 200 ohms

12-18 AWG

speaker circuits
TB20, TB21

untwisted/unshielded,
twisted/shielded, see note

2

determine using Lite-Calcs utility
see note

3

12-18 AWG

ECC-CE6 speaker circuits
TB1 - TB6

untwisted/unshielded,
twisted/shielded, see note

2

determine using Lite-Calcs utility
see note

3

12-18 AWG

external data bus: TB12

twisted/shielded

max loop impedance 13.2 ohms

12-18 AWG

external audio riser: TB22

twisted/shielded

max loop impedance 13.2 ohms

12-18 AWG

external operator interface power:
TB24

untwisted/unshielded,
twisted/unshielded

max loop impedance 13.2 ohms

12-18 AWG

NAC output: TB19

untwisted/unshielded,
twisted/unshielded

refer to Section 2.6.3 , max loop
impedance 120 ohms

12-18 AWG

speaker volume control override:
TB23

untwisted/unshielded,
twisted/unshielded

max loop impedance 120 ohms

12-18 AWG

night ring input: TB16

untwisted/unshielded,
twisted/unshielded

max impedance 30 K ohms

12-18 AWG

external audio input
TB5 (on display board)

twisted/shielded

max loop impedance 100 ohms

12-18 AWG

MNS active, AC loss, and trouble
output relays: TB1 - TB3

untwisted/unshielded,
twisted/shielded, see note

1

depends on the panel monitoring
these outputs

12-18 AWG

auxiliary power: TB17

untwisted/unshielded, see note

1

distance set by 4 VDC max line
drop

12-18 AWG

Table B.1 Wiring Requirements

1 Refer to NEC Standards.
2 Twisted, shielded wire is recommended for maximum protection against EMI and AFI emissions and susceptibility.
3 Must also meet NFPA 72 Standards for minimum and maximum sound levels.

NOTE: Wire to wire short circuit trouble = zero ohms.
Open circuit trouble = infinite ohms.
Ground fault trouble = zero ohms to ground