2 input/output circuit specifications, 1 ecc-50/100 main control board, Input/output circuit specifications – Fire-Lite ECC-50/100E Emergency Command Center User Manual

Page 13: Ecc-50/100 main control board

Advertising
background image

Emergency Command Center Manual —

P/N LS10001-000FL-E:A 4/10/2013

13

Input/Output Circuit Specifications

Product Description

– two Style Y (Class B) or Style Z (Class A) speaker circuits (with optional ECC-50W-

25/70V Audio Amplifier installed)

– eight Style Y (Class B) or Style Z (Class A) speaker circuits (with optional ECC-50W-

25/70V and ECC-CE6 installed)

ECC-50/100 can be controlled by an FACP via the ANN/ACS (EIA-485) link. Compatible

FACPs include the MS-9600(UD)LS and MS-9200UDLS.

Integral supervised microphone

Microphone time-out feature which reverts back to prerecorded message if emergency page

exceeds the programmed time

Up to 14 recorded messages

14 prerecorded messages for fire, emergency, and weather alerts

Field-selectable message and custom message recording capability using the local

microphone, a USB port, or an external audio input

External Audio Input can be used for background music

Up to 60 second message duration for all messages

Integral tone generators field selectable for multiple tone types

Powered by integral AC power supply or batteries during AC fail

Programmable delay of immediate, 2 hours or 6 hours reporting of AC Loss

Piezo sounder for local trouble

100 event history log

Three Form-C relays:
– AC Power Loss Relay - TB1
– System Trouble Relay - TB2
– MNS Active - TB3

500 mA (0.5A) Special Application (auxiliary power) output for addressable modules when

interfaced with compatible addressable FACPs and End-of-Line power supervision relays

System Status LEDs (refer to “Controls and Indicators” on page 20)

Integral Dress Panel

Optional TR-CE semi-flush trim ring

Any combination of up to eight (8) of:
– Optional ECC-RM Remote Microphone (includes cabinet).
– Optional ECC-RPU Remote Page Unit (includes cabinet)
– Optional ECC-LOC (includes cabinet)

Optional ECC-CE6 Circuit Expander

Optional ECC-50W-25V amplifier, 50 watts, 25 volts

Optional ECC-50W-70V amplifier, 50 watts, 70 volts

Optional ECC-50DA distributed amplifier, 50 watts

Optional ECC-125DA distributed amplifier, 125 watts

1.2 Input/Output Circuit Specifications

1.2.1 ECC-50/100 Main Control Board

AC Power - TB15

ECC-50/100: 120 VAC, 60 Hz, 3.5 amps (HOT, NEU)

ECC-50/100E: 240 VAC, 50 Hz, 2.0 amps (HOT=HotLeg1, NEU=HotLeg2)

Wire size: minimum #14 AWG (2.00mm

2

) with 600 V insulation.

Advertising