3 70.7 vrms transformer (ecc-xrm-70v), 14 addressing external data bus devices, 70.7 v – Fire-Lite ECC-50/100E Emergency Command Center User Manual

Page 54: Addressing external data bus devices, 3 70.7 v, Transformer (ecc-xrm-70v)

Advertising
background image

54

Emergency Command Center Manual —

P/N LS10001-000FL-E:A 4/10/2013

Installation

Addressing External Data Bus Devices

2.13.3 70.7 V

RMS

Transformer (ECC-XRM-70V)

The 70.7 V

RMS

Transformer can be used to convert the integral 25 V

RMS

amplifier for installations

where 70.7 V

RMS

speakers already exist or are to be installed. Speaker wiring continues to be

supervised during standby, alarm and while background music is playing when transformer is

installed. The transformer comes pre-installed onto a bracket for mounting to the chassis. Installa-

tion onto the chassis depends on what other option modules are installed. See the ECC-XRM-70V
Installation Document

. Refer to the drawing below.

When installing the ECC-XRM-70V, be sure to:

carefully remove the factory-installed jumper plug from connector J12 on the main control

board.

set SW5 on the ECC-50/100 main control board to 70V operation.

2.14 Addressing External Data Bus Devices

The table below defines an address map for the external data bus devices which include the

ECC-LOC, ECC-RPU, ECC-RM, ECC-50DA, and ECC-125DA. Dipswitches are used on each of

these devices to set the bus address in order to properly communicate with the ECC-50/100 panel.

Any combination of up to eight (8) remote consoles (ECC-LOC, ECC-RPU, and ECC-RM) can be

Figure 2.43 70.7 V

RMS

Transformer Installation

ECC-CE6

e

c

c

x

fm

rc

e

6

.w

m

f

NOTE: For 70.7V

RMS

operation with the optional amplifier, use model ECC-50W-70V.

!

CAUTION:

DISCONNECT POWER

BEFORE INSTALLING ANY MODULES, MAKE CERTAIN ALL POWER (AC AND DC) HAS BEEN
REMOVED.