Emergency Command Center Manual —

P/N LS10001-000FL-E:A 4/10/2013

Installation

Operating Power

2.3 Operating Power

2.3.1 AC Power and Earth Ground Connection

Primary power source for the ECC-50/100 is 120 VAC, 60 Hz, 3.5 amps. Primary power source for

the ECC-50/100E is 240 VAC, 50 Hz, 2.0 amps. Over-current protection for this circuit must com-

ply with Article 760 of the National Electrical Code (NEC) and/or local codes. Make certain that

the AC mains circuit breaker is off before making any wiring connections between the mains and

the panel. Connect AC mains wiring from the protected premises main breaker box to TB15 of the

main control board. Use 14 AWG (2.0 mm2, 1.6 mm O.D.) or heavier gauge wire with 600V insu-

lation. No other equipment may be connected to this circuit and it may not contain any power dis-

connect devices. A separate Earth Ground connection must be made to ensure proper panel

operation and lightning and transient protection. Do not use conduit for the Earth Ground connec-

tion since this does not provide reliable protection. Remove the two keps nuts from the grounding

stud in the backbox. Connect the incoming earth ground wire to supplied cable #71073 with a wire

nut. Position the ring terminal end over the grounding stud. Secure with one of the keps nuts.

Place the ring terminal from the other supplied cable to TB15. Refer to Figure 2.6 for the location

of the stud. Apply AC power to the panel only after the system is completely installed and visually

checked. Note that AC power must be applied to the panel before installing the battery intercon-
nect cable (refer to the following section)

.

!

WARNING: RISK OF EQUIPMENT DAMAGE AND PERSONAL INJURY
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL. DIS-
CONNECT ALL SOURCES OF POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED
EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR INSERTING CARDS, MODULES OR
INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED. BE SURE TO OBSERVE
PROPER GROUNDING AND HANDLING PROCEDURES.

Figure 2.6 Earth Ground Connection

e

c

c

g

n

d

.w

m

f

grounding stud

keps nuts

Grounding
Cable #71073

grounding stud

Equipment
Ground