Emergency Command Center Manual —

P/N LS10001-000FL-E:A 4/10/2013

Programming

Main Menu - User Programming

Log Out

When all programming has been successfully completed, the user must log out to allow

the system to reboot and apply the programming changes.

3.1.2 General/NAC Options

General Options

Unit Operation

Select whether the ECC will function for Fire Evacuation, Mass Notification, or

a Combination of both.

Event Priority

When Combo or Mass Notification is selected for Unit Operation, select whether

Mass Notification

events or Fire Evacuation events will take priority in the system. If Mass Notifi-

cation

is selected as the Unit Operation with the Event Priority set to Fire Evacuation, the ECC will

be a mass notification only system but will allow the FACP to override it if a fire alarm sounds. If
Mass Notification

is selected as the Unit Operation with the Event Priority also set to Mass Notifi-

cation

, the ECC will not have any fire evacuation capabilities and will report mass notification

events to the FACP. In this configuration, FACP outputs can be turned off for mass notification

events if desired.

FACP Data Bus Control

If an FACP will directly communicate with the ECC, select which

communication protocol will be used, ACS-Bus or ANN-Bus.

FACP Data Bus Address This field has no effect on programming and is used for informa-
tional purposes only.

When using the FACP ACS-bus protocol, address 01 must be enabled in the

FACP programming. When using the ANN-Bus protocol, the FACP will automatically detect the

audio system connection during annunciator auto-configuration. No ANN-Bus address selection is

necessary at the FACP. Enter the ECC’s address (1-8) here. If FACP control of the ECC is not

selected, enter 0.

24 Hour Resound

As enabled (default), the 24 Hour Resound feature causes the piezo on the

ECC to sound a reminder ‘beep’ for alarms and troubles after the panel has been silenced.

Class A / Style Z

Select enable if all circuits on the ECC will operate in Class A (Style Z) or dis-

abled

if all circuits will operate in Class B (Style Y).

AC Loss Delay

The reporting of a loss of AC power using the AC Loss relay output can be

delayed by programming the length of the desired delay. The factory default setting is 2 hours.

Options are 0, 2, 6, 12, or 23 hours.

Secondary Amplifier

if an ECC-50W-25/70V is installed, select whether it will be used as a

backup

amplifier or for secondary speaker circuits. If an ECC-50W-25/70V is not installed, select

none

.

Figure 3.3 General Options