Emergency Command Center Manual —

P/N LS10001-000FL-E:A 4/10/2013

Operating Instructions

Operation

4. When the message has finished playing, press the ALL CALL button (or individual speaker

zone buttons pressed in step 2) to deactivate the message areas and continue the evacuation

tone/message.

5. Press the SYSTEM CONTROL button to relinquish control of the audio system.

4.4.3 Fire Alarm Response, System Configured for Fire Only

Upon detection of an alarm condition (any of CMD1 to CMD8 inputs active or automatic activation

from the FACP Data Bus) the system will:

• Turn the appropriate speaker zone LED(s) on steady
• Turn the appropriate speaker circuits on
• Turn the appropriate audio amplifier(s) on
• Turn the 24 VDC aux. power output on (if programmed)
• Turn the speaker volume control override on
• Turn the “System in Use” LED on steady
• Turn the “Fire System Active” LED on steady
• Play a leading tone (if programmed)
• Play and repeat the appropriate audio message (if programmed to repeat)
• Play an inter-message tone (if programmed)
• Play a primary evacuation tone only (if programmed)
• Store the event in the history log

4.4.4 Fire Alarm Restoral, System Configured for Fire Only

Upon restoral the system will:

• Turn the speaker zone LED(s) off
• Turn the speaker circuits off
• Turn the audio amplifier(s) off
• Turn the 24 VDC aux. power output off (if programmed)
• Turn the speaker volume control override off
• Turn the “System in Use” LED off
• Turn the “Fire System Active” LED off

4.4.5 Manual Activation

Upon pressing speaker zone button(s) followed by pressing a message button the system will:

• Turn the appropriate speaker zone LED(s) on steady
• Turn the appropriate speaker circuit(s) on
• Turn the appropriate message LED on steady
• Turn the appropriate audio amplifier(s) on
• Turn the 24 VDC aux. power output on (if programmed)
• Turn the speaker volume control override on
• Turn the “System in Use” LED on steady
• Activate the “MNS active” relay (if the system is programmed for mass notification)
• Activate the NAC output (if programmed to do so for mass notification)
• Play a leading tone (if programmed)
• Play and repeat the appropriate audio message (if programmed to repeat)
• Play an inter-message tone (if programmed)