Emergency Command Center Manual —

P/N LS10001-000FL-E:A 4/10/2013

55

Addressing External Data Bus Devices

Installation

used in the system. Their external data bus addresses must be unique. Note that these four (4) con-

soles occupy two (2) data bus addresses each. The second address is already “reserved” in the sys-

tem for each console. Up to eight (8) distributed amplifiers (ECC-50DA and ECC-125DA) can be

used in the system. Their external data bus addresses must also be unique and sequential. All

addressing must also be set in user programming. Refer to Section 3.1.3 on page 62.
Table 2.1 below shows the dipswitch settings for all possible addresses. Note that some devices

have a 5-position dipswitch while others have a 6-position dipswitch. The sixth switch on these

dipswitches are not used. Dipswitches are shown as they are oriented in the cabinet. Pay close

attention when setting addresses.

Bus Address

Device

Dipswitch Setting

on LOC (SW1)

Dipswitch Setting

on RPU (S11)

Dipswitch Setting

on RM (S1)

0

reserved

n/a

n/a

n/a

1

reserved

n/a

n/a

n/a

2

reserved

n/a

n/a

n/a

3

reserved

n/a

n/a

n/a

4

LOC or RPU or RM #1

5

reserved

n/a

n/a

n/a

6

LOC or RPU or RM #2

7

reserved

n/a

n/a

n/a

8

LOC or RPU or RM #3

9

reserved

n/a

n/a

n/a

10

LOC or RPU or RM #4

11

reserved

n/a

n/a

n/a

12

LOC or RPU or RM #5

13

reserved

n/a

n/a

n/a

14

LOC or RPU or RM #6

15

reserved

n/a

n/a

n/a

16

LOC or RPU or RM #7

17

reserved

n/a

n/a

n/a

18

LOC or RPU or RM #8

19

reserved

n/a

n/a

n/a

5 4 3 2 1

ON

5 4 3 2 1

ON

1 2 3 4 5

ON