5 optional equipment, Optional equipment – Fire-Lite ECC-50/100E Emergency Command Center User Manual

Page 23

Advertising
background image

Emergency Command Center Manual —

P/N LS10001-000FL-E:A 4/10/2013

23

Optional Equipment

Product Description

1.5 Optional Equipment

ECC-50W-25/70V Audio Amplifier Modules

An optional second audio amplifier can be plugged into connectors J10 & J11 located in the upper

right of the main control board in the ECC-50/100. This amplifier also provides 50 watts of power

at 25 V

RMS

or 70 V

RMS

, depending on the model, and can therefore be used to expand system power

to 100 watts (providing dual 50 watt speaker circuits) or it can be used as a backup amplifier. The

output is power-limited (Class 2) and speaker circuit connections to it are provided on the main

control board and optional speaker circuit expander module. The circuit can be wired for Style Y

(Class B) or Style Z (Class A) operation.
LEDs are provided to indicate Amplifier Supervision (green indicates amplifier is functional) and

Circuit Trouble (yellow indicates field wiring fault or amplifier fault). The LEDs are only visible

with the panel door open.

ECC-CE6 Circuit Expander Module

This optional module plugs into connector P1 in the upper middle of the main control board. The

ECC-CE6 adds three primary speaker circuits to the ECC-50/100. The ECC-CE6 adds three sec-

ondary circuits to the system when the ECC-50W-25/70V Audio Amplifier Module is also

installed.

ECC-XRM-70V Transformer 70.7 V

RMS

This optional module plugs into connector J12 of the main control board and provides conversion

for the integral audio amplifier from 25 V

RMS

to 70.7 V

RMS

at full rated 50 watts output power.

ECC-FFT Fire Fighter Telephone

The ECC-FFT has a telephone handset and user interface that allows an operator to communicate

with remotely located telephone handsets in a building. It is housed in its own cabinet with key

lock. It requires an external operator interface power connection (24 volts DC) from the ECC-

50/100 main console or it may be powered from an external 24 VDC power supply such as

HP300ULX. The ECC-FFT provides supervision, annunciation, and control for the local handset

and for up to 24 remote telephone handsets. It provides indications of phone activation and corre-

sponding trouble conditions. Refer to the ECC-FFT Fire Fighter Telephone manual.

ECC-50DA Distributed (Remote) Audio

The ECC-50DA is a 50-watt audio amplifier (audio booster) with its own cabinet and key lock. It

requires an external data bus connection and an external audio riser connection from the ECC-

50/100 main console. The unit comes standard with 4 speaker circuits. An option card, ECC-CE4,

provides 4 more speaker circuits for a total of 8. Speaker circuits are activated/de-activated manu-

ally or automatically by the ECC-50/100 main console. The unit is capable of either 25 V

RMS

or

70.7 V

RMS

operation. Refer to the ECC-50/125DA Distributed Audio manual.

ECC-125DA Distributed (Remote) Audio

The ECC-125DA is a 125-watt audio amplifier (audio booster) with its own cabinet and key lock. It

requires an external data bus connection and an external audio riser connection from the ECC-

50/100 main console. The unit comes standard with four (4) speaker circuits. An option card, ECC-

CE4, provides 4 more speaker circuits for a total of eight (8). Speaker circuits are activated/de-acti-

vated manually or automatically by the ECC-50/100 main console. The unit is capable of 25 V

RMS

operation. Refer to the ECC-50/125DA Distributed Audio manual.

NOTE: Any combination of up to eight audio boosters comprised of ECC-50DA and ECC-125DA
can be used in the system. Their external data bus addresses must be unique and must be
sequential. Addresses are set via dipswitches on each unit's PC board. Refer to Section 2.14 on
page 54.