8 ecc-rpu remote page unit – Fire-Lite ECC-50/100E Emergency Command Center User Manual

Page 43

Advertising
background image

Emergency Command Center Manual —

P/N LS10001-000FL-E:A 4/10/2013

43

ECC-RPU Remote Page Unit

Installation

2.8 ECC-RPU Remote Page Unit

Connections are made from TB24, TB12, and TB22 on the ECC-50/100 main control board to

TB1, TB3, and TB2 on the RPU. If the ECC-RPU is the last device on the audio and data bus

chain, signal terminations are required. For the external data bus, a removable jumper must be on

pins 1 and 2 of JS4. If the ECC-RPU is not the last device, the jumper must be on pins 2 and 3 of

JS4 as shown below. For the external audio riser, termination ELR-15K must be connected to pins

4 and 5 on TB2. T-taps and multiple home runs to the main control board are not allowed for the

external data bus or the external data riser.

+

-

+

-

+

-

+

-

+

-

+

-

B
A

B
A

B
A

main control board

RPU board

TB24

TB12

TB22

TB1

TB3

TB2

external operator interface power - 24VDC

external

data bus

external

audio

riser

to next operator

interface or amplifier

rp

u

w

ir

e

b

.w

m

f

Figure 2.24 Remote Page Unit Wiring (Class B/Style Y)

to next operator

interface or amplifier

to next operator

interface or amplifier

JS4

(shown jumpered

on pins 2 and 3)