3 ecc-ce6 circuit expander module, Ecc-ce6 circuit expander module – Fire-Lite ECC-50/100E Emergency Command Center User Manual

Page 19

Advertising
background image

Emergency Command Center Manual —

P/N LS10001-000FL-E:A 4/10/2013

19

Input/Output Circuit Specifications

Product Description

1.2.3 ECC-CE6 Circuit Expander Module

Power-limited (Class 2) circuitry

Up to six (6) circuits on the ECC-CE6 can be wired as Style Y (Class B) or Style Z (Class A).

Normal Operating Voltage for Speaker Circuits: 25 V

RMS

@ 2 amps max. and maximum Load

Impedance of 12.5

(70.0 V

RMS

@ 700 mA max. with maximum Load Impedance of 100operation possible for

the primary circuit by plugging optional ECC-XRM-70V conversion transformer into J12 of

the main control board. The same operation is possible for the optional 50W amplifier by

selecting the ECC-50W-70V model.)

Speaker circuit wiring is supervised during standby, background music, and alarm.

Output Power: 50 watts total; Frequency Range: 800 - 2,800 Hz

Maximum total capacitance: 250 µF. (Note that the total capacitance for the speaker outputs must
not exceed the maximum of 250 µF).

End-of-Line Resistor required for Style Y (Class B) speaker circuit: 15 K, 1 watt (P/N: ELR-15K)

TB13 on the main control board: ACS/ANN (EIA-485) electrically isolated link to FACP provides

programmed speaker control

Advertising
This manual is related to the following products: